background image

Page 13

16400-7800 GSS REV D

5 - MANTEL REQUIREMENTS

NON-COMBUSTIBLE ZONE - 

NOT 

USING THE PROVIDED 1/2" STANDOFFS

Figure 5.2

NOTE: Refer to Page 33 for more information on fi nishing the wall. 

The fi replace has standoff s installed on the front of the fi replace standard from the factory. They are located on the left, 
center and right front hood of the fi replace and are to ensure that the 1/2" [12.7mm] required clearance to combustibles 
on the surface of the fi replace is maintained. 

If the standoff s are removed, only non-combustible material can be installed against the surface of the fi replace such as 
a non-combustible backer cement board. 1/2” [12.7mm] minimum thickness must be used in the 15” [381mm] between 
the top of the 3’’ trim to the combustible framing the full width of the fi replace. The 15” includes a 7” [178mm] minimum 
above the top of the fi replace that is recommended for ease of attachment.

Refer to Figure 5.2 on below for requirements when not using the provided 1/2" standoff s. 
Refer to Figure 5.1 on Page 12 for a standard installation using the provided 1/2" standoff s. 

1/2" [12.7mm] Standoff 

Содержание 4-SS-2-GL

Страница 1: ...trical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING If the information in these instructions are not followed exactly a fire or exp...

Страница 2: ...INS_CUST UL REV D Page 2 ...

Страница 3: ... 1 Roof Termination Cap Installation With Damper 22 H 2 Roof Termination Cap Installation Without Damper 22 I 1 Wall Termination Cap Installation With Damper 23 I 2 Wall Termination Cap Installation Without Damper 23 J Outside Air Intake 24 K Changing Outside Air From The Side To The Bottom 24 12 Pressure Testing 36 Inlet Pressure Test 36 13 Finalizing The Installation 36 A Installing The Glass Me...

Страница 4: ...hould be done by a qualified service technician Clean glass only when cool and only with non abrasive cleansers Do not operate this appliance with the glass frame assembly removed cracked or broken Replacement of the glass assembly must only be performed by a licensed or qualified service person DO NOT SUBSTITUTE MATERIALS Do not strike or slam glass assembly Keep burner and control compartment clea...

Страница 5: ... 8 987 24 1 32 610 77 3 4 1 975 7 SS 2 GL 10 10 86 3 16 2 189 24 610 42 1 067 50 1 270 44 7 8 1 140 24 1 32 610 89 3 4 2 280 4 SS 3 GL 8 10 50 3 16 1 275 36 914 54 1 372 62 1 575 26 7 8 683 24 1 32 610 53 3 4 1 365 5 SS 3 GL 8 10 62 3 16 1 580 36 914 54 1 372 62 1 575 32 7 8 835 24 1 32 610 65 3 4 1 670 6 SS 3 GL 10 10 74 3 16 1 884 36 914 54 1 372 62 1 575 38 7 8 987 24 1 32 610 77 3 4 1 975 7 SS...

Страница 6: ...FOR MORE INFORMATION SPECIFICATIONS Model B VENT OA REG PV IN LINE PV BTU S NG ORIFICE LP ORIFICE 4 SS 2 GL 4X2 SINGLE SIDED 8 10 RSO12 RSIF160 60 000 3X 43 3X 55 5 SS 2 GL 5X2 SINGLE SIDED 8 10 RSO12 RSIF160 80 000 4X 43 4X 55 6 SS 2 GL 6X2 SINGLE SIDED 10 10 RSO14 RSIF180 100 000 5X 43 5X 55 7 SS 2 GL 7X2 SINGLE SIDED 10 10 RSO14 RSIF180 120 000 6X 43 6X 55 4 SS 3 GL 4X3 SINGLE SIDED 8 10 RSO12 ...

Страница 7: ... Complete venting installation 9 Install facing material mantel or cabinetry 10 Install glass media natural stone and any interior options including mirrors and or driftwood log set 11 Verify proper operation of fireplace and all components D PLACEMENT CLEARANCE REQUIREMENTS This fireplace must be installed on a level surface capable of supporting the fireplace and venting Fireplace must be placed di...

Страница 8: ...ure 3A 2 Fold the center of the standoff up and both ends out at the perforated lines Using Figure 3A 2 for reference locate the second pre installed screw on the firebox top at each standoff location Remove the screw pivot the folded standoff into location and re install the screw to secure the standoff Tighten up the screw that was loosened in Step 1 PIVOT FOLDED STANDOFF AND SECURE LOOSENED SCREW Si...

Страница 9: ...Figure 3A 3 for reference locate the pre drilled holes on the firebox side each nailing flange will be placed at STEP 3 Refer to Figure 3B 3 Figure 3B 4 Set each nailing flange in place and secure using two 2 screws each Bend the nailing flange out from fireplace at the remaining perforated line The nailing flanges will ensure the 1 minimum clearance is kept to combustible framing Refer to Figure 3B 5 D...

Страница 10: ...hearth extension is desired combustible material may be used CAUTION Install fireplace on metal concrete or hard wood surface extending the full width and depth of fireplace CAUTION Vent cap location must be in compliance with guidelines on pages 15 19 of this manual NOTE DO NOT PIERCE ANY OF THE BLACK PAINTED SURFACES WITH SCREWS RIVETS ETC THIS INCLUDES THE 3 BLACK TOP AND BOTTOM GLASS TRIM AND AN...

Страница 11: ...ANT FRAMING NOTES FRAMING SHOULD BE BUILT AFTER THE FIREPLACE IS INSTALLED OR EXTRA CLEARANCE MUST BE PLANNED FOR AT THE INTAKE COLLAR THESE DIMENSIONS REPRESENT THE FRAMING DIMENSIONS FOR COMBUSTIBLE MATERIAL NON COMBUSTIBLE FRAMING AND FINISHING MATERIALS MAY BE USED WITHIN THESE DIMENSIONS RIGHT UP TO THE UNIT NO COMBUSTIBLE MATERIAL WITHIN 6 152 OF THE TOP OF THE FIREPLACE NO COMBUSTIBLE MATER...

Страница 12: ...s on the surface of the fireplace is maintained If the standoffs are removed only non combustible material can be installed against the surface of the fireplace such as a non combustible backer cement board 1 2 12 7mm minimum thickness must be used in the 15 381mm between the top of the 3 trim to the combustible framing the full width of the fireplace The 15 includes a 7 178mm minimum above the top of...

Страница 13: ... of the fireplace is maintained If the standoffs are removed only non combustible material can be installed against the surface of the fireplace such as a non combustible backer cement board 1 2 12 7mm minimum thickness must be used in the 15 381mm between the top of the 3 trim to the combustible framing the full width of the fireplace The 15 includes a 7 178mm minimum above the top of the fireplace th...

Страница 14: ...DONE BY A LICENSED OR QUALIFIED SERVICE PERSON WARNING DO NOT REMOVE GLASS ASSEMBLY WHEN HOT NOTE GLASS REMOVAL AND INSTALLATION MUST BE PERFORMED WITH TWO PEOPLE NOTE Glass must be removed using quality suction cups DO NOT attempt to remove the glass without using proper suction cups Figure 6B 1 NOTE IN CASE OF CHIPPED OR BROKEN GLASS Due to the size and sensitivity of shipping the glass separate...

Страница 15: ...s carefully making sure to protect the edges 2 Apply the suction cups to the inner glass assembly following instructions included with the suction cups 3 Lift the glass into place The top edge slips into the top groove lift into the groove until the bottom is clear of the bottom trim Slide the glass down into the inner bottom grove See Figure 6A 4 Push vertical glass trim into place on each side S...

Страница 16: ...UTION Installation of the gas line must only be done by a qualified person in accordance with local building codes if any If not follow ANSI 223 1 NOTE The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at pressures in excess of psi NOTE The appliance must be isolated from the gas supply piping system by cl...

Страница 17: ...s as outlined in this manual SEE CHART ABOVE FOR SIZE diameter B Type Venting that must be used UL CSA approved B Vent only DO NOT decrease the vent size Vent runs are approved for up to 110 feet with quantity of 11 90 degree elbows This is not the case with all instances You must have venting scenario approved by Stellar Hearth Products Available In Line Power Venting An in line power vent RSIF s...

Страница 18: ... INCLUDED WITH FIREPLACE Purchase this adapter with the applicable B Vent brand or vent pipe used The increaser will connect directly to the 8 outlet collar of the powervent Then connect your 10 B Vent to the collar and continue the vent run 8 to 10 Increaser 8 10 EXHAUST SIDE RSIF 180 D IN LINE POWERVENT PREPARATIONS RSIF 180 When installing a fireplace in conjunction with the Enervex RSIF In Line...

Страница 19: ...tion on window D Ventilated soffit 24 610 mm E Unventilated soffit 12 305 mm F Outside corner 12 305 mm G Inside corner to non combustibles 12 305 mm H Meter Regulator Not to be installed above a gas meter regulator assembly within 3 ft 914 mm horizontally from the center line of the regulator I Gas Service regulator vent outlet 3 ft 914 mm J Non mechanical air supply inlet to building or the combusti...

Страница 20: ...INS_CUST UL REV D Page 20 Figure 8F 2 F HORIZONTAL TERMINATION VENT CAP LOCATION CLEARANCES 8 VENTING ...

Страница 21: ...25 0 38 OVER 7 12 TO 8 12 1 5 0 46 OVER 8 12 TO 9 12 2 0 0 61 OVER 9 12 TO 10 12 2 5 0 76 OVER 10 12 TO 11 12 3 25 0 99 OVER 11 12 TO 12 12 4 0 1 22 OVER 12 12 TO 14 12 5 0 1 52 OVER 14 12 TO 16 12 6 0 1 83 OVER 16 12 TO 18 12 7 0 2 13 OVER 18 12 TO 20 12 7 5 2 27 OVER 20 12 TO 21 12 8 0 2 44 3 foot minimum in snowy regions Figure 8G 8 VENTING ...

Страница 22: ..._CUST UL REV D Page 22 H ROOF TERMINATION CAP INSTALLATION WITH AND WITHOUT DAMPER 8 VENTING Roof Termination Without Optional Damper Roof Termination With Optional Damper Figure 8H 1 Figure 8H 2 OPTIONAL ...

Страница 23: ...REV D I WALL TERMINATION WITH AND WITHOUT DAMPER 8 VENTING Wall Termination Without Optional Damper Wall Termination With Optional Damper Figure 8I 1 Figure 8I 2 FRAMING 8 11 3 4 W X 11 3 4 H 10 13 1 4 W X 13 1 4 H H OPTIONAL ...

Страница 24: ...e Use Table 8J 2 for reference on CFM replacement air if drawing intake air from inside the house and open air requirements for intake screen vent or consult Stellar Hearth Products for more information Step 1 Remove 4 screws that hold collar plate in place Refer to Figure 8K 1 Step 2 Slide collar plate off fireplace Refer to Figure 8K 2 Step 4 Re attach the plate with four screws Refer to Figure 8K...

Страница 25: ...side rear and bottom on the pilot side of the fireplace You also have access from inside the fireplace It is important when planning how you are going to finish off the fireplace and take in consideration which access point you are going to use for any service at a later date For more information on how to access from the inside see Valve Electrical Access under Maintenance Section 14 Figure 9A ...

Страница 26: ...INS_CUST UL REV D Page 26 9 GALAXY ELECTRIC Figure 9B B INSTALL ...

Страница 27: ...Page 27 16400 7800 GSS REV D 9 GALAXY ELECTRIC C SERVICE TROUBLESHOOTING Figure 9C ...

Страница 28: ...INS_CUST UL REV D Page 28 9 GALAXY ELECTRIC Figure 9D 1 Terminals 1 2 D 1 TERMINALS 1 2 LED Lights Figure 9D 2Terminals 3 4 D 2 TERMINALS 3 4 Main Flame ...

Страница 29: ...Page 29 16400 7800 GSS REV D 9 GALAXY ELECTRIC Figure 9D 3 Terminals 5 6 D 3 TERMINALS 5 6 Fireplace Power Figure 9D 4 Terminals 7 8 D 4 TERMINALS 7 8 Powervent Connection ...

Страница 30: ...INS_CUST UL REV D Page 30 9 GALAXY ELECTRIC Figure 9D 5 Terminals 9 10 D 5 TERMINALS 9 10 OPTIONAL Flue Damper Connection OPTIONAL ...

Страница 31: ...Page 31 16400 7800 GSS REV D Figure 9D 6 Terminals 11 12 D 6 TERMINALS 11 12 OPTIONAL Flue Damper Connection 9 GALAXY ELECTRIC OPTIONAL ...

Страница 32: ...IM AND ANY PAINTED SIDES ADJACENT TO THE GLASS NOTE REFER TO DIMENSIONS SECTION FOR ALLOWABLE FINISHING DIMENSIONS REQUIRED TO FIT THE GLASS PANELS INTO THE FIREPLACE FINISHING MATERIALS MUST NOT OVERLAP THE DIMENSIONS HIGHLIGHTED IN GREEN ON PAGE 5 NEVER COVER THE GLASS WITH FINISHING MATERIALS NOTE REFER TO MANTEL REQUIREMENTS NON COMBUSTIBLE ZONE USING PROVIDED 1 2 STANDOFFS FOR MORE INFORMATIO...

Страница 33: ...NISHING MATERIALS MUST NOT OVERLAP THE DIMENSIONS HIGHLIGHTED IN GREEN ON PAGE 5 NEVER COVER THE GLASS WITH FINISHING MATERIALS NOTE REFER TO MANTEL REQUIREMENTS NON COMBUSTIBLE ZONE USING PROVIDED 1 2 STANDOFFS FOR MORE INFORMATION PAGE 13 Figure 10A 2 NOTE DO NOT PIERCE ANY OF THE BLACK PAINTED SURFACES WITH SCREWS RIVETS ETC THIS INCLUDES THE 3 BLACK TOP AND BOTTOM GLASS TRIM AND ANY PAINTED SI...

Страница 34: ...ance if any part has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system which has been under water WHAT TO DO IF YOU SMELL GAS Do not touch any electrical switches Do not try to light any appliance Do not use the phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas suppli...

Страница 35: ...replace on at switch Figure 11B 11 LIGHTING SHUTDOWN STOP Read safety information on previous page and front cover of this manual before continuing NOTE This fireplace is equipped with an ignition device which automatically lights the pilot DO NOT try to light the pilot by hand CAUTION If fireplace will not operate follow instructions TURNING OFF GAS TO FIREPLACE and call your service technician or ...

Страница 36: ...MEDIA WITH ANY OTHER KIND OF MEDIA WITHOUT WRITTEN APPROVAL OF STELLAR HEARTH PRODUCTS Figure 13A Place the supplied glass media into the base tray Cover the base evenly Do not use more than the supplied amount Do not get any glass media into the pilot area a hazardous condition could result You should be able to see the burner slightly through the media If you can t push the media back from the b...

Страница 37: ...ent Enervex SEE PAGE 17 Valve Honeywell Smart Valve SV9501 Pilot Honeywell Smart Valve Q3450C1185 Vacuum Switch Cleveland Controls AFS 405 Flue Pipe Approved SEE PAGE 17 24vac Transformer Dayton 24vac 40 VA Orifices Custom SEE PAGE 6 Glass Media CRYSTAL Glass Panel Sizes CONTACT STELLAR DIRECTLY VALVE AND ELECTRICAL ACCESS There is an access panel under the floor of the firebox should more extensive ...

Отзывы: