Page 16
GAS LINE CONNECTION
Propane
Natural
MINIMUM INLET GAS PRESSURE
11.0 inches W.C.
(recommended)
7.0 inches W.C.
(recommended)
MAXIMUM INLET GAS PRESSURE
14.0 inches W.C.
10.0 inches W.C.
MANIFOLD PRESSURE (HI)
10.0 inches W.C.
3.5 inches W.C.
ORIFICE SIZE
SEE CHART ON PAGE 6
SEE CHART ON PAGE 6
INPUT BTU/HR
SEE CHART ON PAGE 6
SEE CHART ON PAGE 6
Figure 7
7 - GAS LINE SPECIFICATIONS
This fi replace is manufactured for use with Natural Gas or Propane.
CAUTION: Installation of the gas line must only be done by a qualifi ed person in accordance with local building codes, if any.
If not, follow ANSI 223.1.
NOTE: The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any
pressure testing of that system at pressures in excess of ½ psi.
NOTE: The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve
during any pressure testing of the gas line at test pressures equal to or less than ½ psi (3.5 kPa).
NOTE: For high altitude installations, consult Stellar Hearth Products directly for proper rating methods.
Figure 7
1/2" Gas Supply