INS_CUST UL REV E
Page 44
11 - FINISHING
A.1 FINISHING THE WALL - USING THE PROVIDED 1/2" STANDOFFS -
INTERIOR
A
1" [25]
C. COMBUSTIBLE OR NON-COMBUSTIBLE
FINISHING MATERIAL
INTERIOR
B
D - NON-COMBUSTIBLE BOARD OR COMBUSTIBLE BACKER MATERIAL
(I.E. SHEET ROCK/OSB)
I - DECORATIVE FRAME
DO NOT OVERLAP WITH
FINISHING MATERIALS
G (IN) - ACCESS PANEL
E - COMBUSTIBLE MANTEL
F - COMBUSTIBLE HEARTH
COMBUSTIBLE FRAMING
H - COMBUSTIBLE FRAMING
AND FINSIHING MATERIAL
A. No combustible materials may be within 6” [152] of the top of the fireplace.
B. 1/2” [13] CLEARANCE TO COMBUSTIBLES ON SURFACE. The fireplace ships with standoffs in place to ensure a 1/2” [13]
clearance to combustibles is maintained on the surface. See Figure 10A.1. If the standoffs are removed, only non-combustible
material can be installed against the surface of the fireplace such as a non-combustible backer cement board. 1/2” [13] minimum
thickness must be used in the space* between the top of the 3’’ trim to the combustible framing the full width of the fireplace.
The space* includes a 7” [76] minimum above the top of the fireplace that is recommended for ease of attachment.
*= 15" [381] for 3'-7' units and 19" [483] for 8' units. See Figure 10A.2
C. Combustible material may cover the non-combustible area mentioned in B.
D. Combustible finishing materials allowed.
E. Combustible mantel may be placed above the top of the decorative frame area. There are no restrictions on mantel depth.
F. Combustible hearth may be placed below the bottom of the decorative frame area.
G. (IN) Flat covers will cover the components access. Gas and electric inlets are located behind this panel. There are three access
panel options all located on the pilot side of the fireplace; interior front (shown above), side, and inside behind the glass.
Please take consideration of which option will be used to access the components for service later during planning.
H. Combustible framing and finishing materials allowed.
I. The 3” [76] surface behind the decorative glass frame (not shown) can not be covered with any type of material. The glass and
decorative frame will be placed on top of this surface. Fasteners must not penetrate the 3” [76] surface.
= [millimeters]
NOTE: REFER TO DIMENSIONS SECTION FOR ALLOWABLE FINISHING DIMENSIONS REQUIRED TO FIT THE GLASS
PANELS INTO THE FIREPLACE. FINISHING MATERIALS MUST NOT OVERLAP THE DIMENSIONS HIGHLIGHTED IN GREEN ON
PAGE 5. NEVER COVER THE GLASS WITH FINISHING MATERIALS.
NOTE: REFER TO SECTION 5 FRAMING & MANTEL REQUIREMENTS: NON-COMBUSTIBLE ZONE USING PROVIDED 1/2"
STANDOFFS FOR MORE INFORMATION.
Figure 11A.1