5 - FRAMING & MANTEL REQUIREMENTS
5.2 NON-COMBUSTIBLE ZONE -
NOT
USING THE PROVIDED 1/2" STANDOFFS
COMBUSTIBLE HEARTH
COMBUSTIBLE FACING
MATERIAL
SIDE GLASS FRAME
- DO NOT COVER -
COMBUSTIBLE OR NON-COMBUSTIBLE
BACKING MATERIAL (I.E. SHEETROCK)
COMBUSTIBLE OR
NON-COMBUSTIBLE MATERIAL
NON-COMBUSTIBLE
MATERIAL WHEN
1/2” [12] STANDOFFS
REMOVED
8”
BOTTOM GLASS FRAME
DO NOT COVER
3” [76]
THIS EXAMPLE OF FRAMING AND FINISHING IS FOR REFERENCE.
PLEASE MAKE SURE TO MAKE CONSIDERATIONS FOR THE FRAMING AND FINISHING
MATERIALS THAT YOU ARE USING FOR YOUR PARTICULAR INSTALLATION.
GLASS VIEWING AREA
3” [76]
THE 3” [76.2] STEEL SURFACE AROUND
THE FIREPLACE OPENING CAN NOT BE
COVERED WITH ANY MATERIAL.
GLASS AND DECORATIVE FRAMING WILL
BE PLACED ON TOP OF IT.
EXTERIOR
TOP GLASS FRAME
DO NOT COVER
COMBUSTIBLE FRAMING
12”
[305]
COMBUSTIBLE MANTEL
7” ABOVE TOP OF FIREPLACE
If the standoffs are removed, only non-combustible material can be
installed against the surface.
1/2” [12.7mm] minimum thickness must be
used between the top of the 3” trim extending 12” [304.8mm] high the full
width of the fireplace. The 12” includes a 7” [178mm] minimum above
above the top of the fireplace that is recommended for ease of attachment.
6” [152 mm]
MINIMUM NON-COMBUSTIBLE ZONE
MINERAL WOOL ONLY IN THIS SPACE
COMBUSTIBLE HEARTH ON
EXTERIOR NEEDS TO BE PLACED
UNDERNEATH AIR INTAKE VENTS
AIR INTAKE VENTS
Important Note: Exterior Hearth
You must properly flash and slope the hearth so water drains away from the wall.
EXTERIOR FLANGE
[MILLIMETERS]
INTERIOR SHOWN.MANTEL AND FRAMING EXAMPLE
APPLIES TO BOTH SIDES FOR SEE THROUGH FIREPLACE.
Figure 5.2