Commissioning
A
D
B
C
Navigating the display
X
Button (A) Escape
X
Buttons (B) and (C) Arrow buttons Up and Down:
X
Button (D) Enter
Table of countries
The following table shows the values determined by the countries.
Grid voltage
(Disconnection value)
Grid frequency
(Disconnection value)
System impedance
monitoring
Reconnecion-
time
Default
–10 % / + 6 % of the
rated voltage (0.1 s)
+/–0.2 Hz of the rated
frequency (0.2 s)
Yes, in accordance with
VDE 0126-1-1
180 s
3000
Greece
–20 % / + 15 % of the
rated voltage (0.5 s)
+/–0.5 Hz of the rated
frequency (0.5 s)
Yes, in accordance with
VDE 0126-1-1
180 s
3300
1)
France (Germany)
–20 % / +15 % of the
rated voltage (0.2 s)
–2.5 / + 0.2 Hz of the
rated frequency (0.2 s)
Not applicable
30 s
3400
Spain
–20 % / +15 % of the
rated voltage (0.2 s)
+/–0.6 Hz of the rated
frequency (0.2 s)
Not applicable
30 s
3510
Portugal
–20 % / +15 % of the
rated voltage (0.2 s)
–2.5 / +0.2 Hz of the rated
frequency (0.2 s)
Yes, in accordance with
VDE 0126-1-1
30 s
3900
Italy
–20 % / +20 % of the
rated voltage (0.1 s)
+/–0.3 Hz of the rated
frequency (0.1 s)
Not applicable
30 s
3901
Italy
–20 % / +20 % of the
rated voltage (0.1 s)
+/–1 Hz of the rated
frequency (0.1 s)
Not applicable
30 s
4400
Great Britain
–10 % / +15 % of the
rated voltage (1.5 s)
+/–1 Hz of the rated
frequency (0.5 s)
Not applicable
180 s
1)
Select
3300 France
before using the inverter in Germany.