7 Technical data
StecaGrid 1900 D Master
StecaGrid 1900 Slave
Input data (PV side)
Input voltage, working range (V
mppmin
… V
mppmax
)
80 V … 400 V DC
Rated input voltage DC (V
dc,r
)
300 V DC
Maximum start voltage (V
dcstart
)
410 V DC
Maximum input voltage for feeding electricity (V
dcmax
)
450 V DC (higher voltages can damage the device)
Minimum input voltage for grid-feeding (V
dcmin
)
> 80 V
Disconnection voltage
50 V
Rated input current DC
6.7 A DC
Maximum input current (I
dcmax
)
2 x 8 A DC [current limited by inverter]
or
1 x 16 A DC [parallel inputs]
Isolation principle
HF transformer with galvanic isolation and Increased isolation
Thermal monitoring
Yes
Reverse polarity protection
Yes
Maximum DC input power
1,000 W [per input]
or
1,000 W [2 parallel inputs]
Maximum recommended PV power
2,200 Wp
Reduction in power / Restriction
Automatic when
- input power is higher (> 1.000 kW/input)
- the equipment is not cooled enough
- input currents > 2 x 8 A DC or 1 x 16 A (parallel inputs).
(Higher currents are restricted by the equipment and therefore will not damage the inverter)
DC connections
MultiContact MC 4 (Solarline 2)
Output data (grid-side)
Output nominal power (P
ac,r
)
1,840 W AC
Maximum output power
1,840 W AC
Grid voltage (V
acmin
… V
acmax
)
190 ... 265 V AC [depending on regional settings]
Grid type
L/N + PE
Grid frequency (f
min
… f
max
)
57,2 ... 62 Hz [depending on regional settings]
Rated output current (P
ac,r
)
8 A AC at 230 V AC
Maximum output current (I
acmax
)
9.7 A AC
Power factor
> 0,95
Distortion factor
< 5 % (at maximum output)
Disconnection value during stand-alone operation
[See table of countries (enclosed)]
Maximum efficiency
95 %
European efficiency (
η
EU
)
93.3 %
93.5 %
MPP efficiency
> 99%
Efficiency at part load (5, 10, 20, 30, 50, 100 % of nominal power)
78,8 %, 86,8 %, 91,7 %, 93,3 %, 94,4 %, 95,0 % 80,2 %, 87,5 %, 92,0 %, 93,5 %, 94,6 %, 95,1 %
Efficiency reduction in the case of a rise in ambient temperature (with tempera-
tures >40 °C)
2 %/°C
Efficiency reduction in the case of deviation from the DC rated voltage
0,006 %/V
Ambient temperature range (Tamb.)
-25 ... +60 °C
Power derating at full power
From 45° (Tamb.)
Start-up power
20 W
Shut-down power
18 W
Stand-by power
3 W
Inverter's own consumption (nighttime operation)
1.3 W
0 W
AC connection cable
WAGO 1.5 - 10 mm² (flexible) / 16 mm² (solid)
via master
Standards and certification marks
EMC
EN 61000-6-3 (EN 55014 and EN 55022 class B)
EN 61000-6-2
Safety directive
EN 62103 (EN 50178) and EN 60950 *
Protection degree
IP65
IP65
Overvoltage category
III
Humidity
0 ... 95 %
Certification mark
Document of compliance, CE
Dimensions and weight
Dimensions (W x H x D):
351 x 542 x 140 mm
226 x 535 x 140 mm
Weight:
approx. 11 kg
approx. 9 kg
Other
Grid monitoring
Compliant with
DIN VDE 0126-1-1
-
Isolation monitoring
None, because of galvanic isolation through the HF transformer in the device
Display
Display, LED
-
Noise level
< 32 dBA
* extended with the requirements of the draft IEC 62109-1/-2.