C O N F I G U R A T I O N & O P E R A T I O N
Icon status
An icon status located at the right hand side in the footer of the screen indicate the status of
the
IER
IER is OK and in opera on or stand by.
Alarm level 1, needs service technician reset if latched.
Alarm level 2, auto reset as soon as default is over.
Communica on between board computer and Main controller is altered.
Service is required.
IER states
The different possible states of the IER are:
STANDBY_STATE,
IER is disable (see status of enable bu on in Control se ng / control config).
ARMED_STATE,
IER is ready to operate, wai ng for humidity demand
STEAM_ON_STATE,
IER is producing steam
DRAINCYCLE_STATE,
IER is draining the cylinder
ADD_WATER_STATE,
IER is adding water in the cylinder (while producing steam or not)
PRE_HEAT_STATE,
If Preheat func on is enable, the IER is hea ng water in the cylinder.
ALARMS_STATE,
IER is on Alarm of level 1, a manual reset is required, go to Humidifier se ngs / Reset
alarm.
SERVICE_STATE,
User has ordered a drain for service, in this case
IER
will drain the cylinder, refill with
fresh water in case the temperature inside cylinder is above 140°F [60°C] (if cooling
func on is enabled), and drain again.
34