C O N F I G U R A T I O N & O P E R A T I O N
Overview screen
Overview screen gives all informa on on internal sensors and control se ngs and allow
ordering a drain for service
Current state of the
IER humidifier
Order drain for
service
1) select steam
generator
2) click on start;
Drain pump will
operate. If water
temperature is
between 140 to
212°F [60 to
100°C] cylinder
will be cooled off
by filling up with
fresh water and
draining it a 2nd
me.
IER state will
change to
‘’SERVICE’’
Control
configura on
summary
Figure 36 – overview screen