5

Do not cover the temperature & pressure relief valve.

Do not cover the instruction manual. Keep it on the side of the water
heater or nearby for future reference.

Do obtain new labels from State for placement on the blanket directly
over the existing labels.

LOCATING THE HEATER

 

WARNING

THERE IS A RISK IN USING FUEL BURNING APPLIANCES SUCH AS GAS
WATER HEATERS IN ROOMS, GARAGES OR OTHER AREAS WHERE
GASOLINE, OTHER FLAMMABLE LIQUIDS OR ENGINE DRIVEN EQUIPMENT
OR VEHICLES ARE STORED, OPERATED OR REPAIRED. FLAMMABLE
VAPORS ARE HEAVY AND TRAVEL ALONG THE FLOOR AND MAY BE
IGNITED BY THE HEATER’S IGNITER OR MAIN BURNER FLAMES CAUSING
FIRE OR EXPLOSION. SOME LOCAL CODES PERMIT OPERATION OF GAS
APPLIANCES IF INSTALLED 18 INCHES (46 cm) OR MORE ABOVE THE
FLOOR. THIS MAY REDUCE THE RISK IF LOCATION IN SUCH AN AREA
CANNOT BE AVOIDED.

THE HEATER SHALL BE LOCATED OR PROTECTED SO IT IS NOT SUBJECT
TO PHYSICAL DAMAGE BY A MOVING VEHICLE.

DO NOT LOCATE THE HEATER WHERE NOISE FROM THE EXHAUST OR
INTAKE WILL BE OBJECTIONABLE. THIS INCLUDES LOCATIONS CLOSE TO
OR ACROSS FROM WINDOWS AND DOORS. AVOID ANCHORING THE VENT
AND INTAKE PIPES DIRECTLY TO FRAMED WALLS, FLOORS OF CEILINGS
UNLESS RUBBER ISOLATION PIPE HANGERS ARE USED. THIS PREVENTS
ANY VIBRATIONS FROM BEING TRANSMITTED INTO THE LIVING SPACES.

 

WARNING

FLAMMABLE ITEMS, PRESSURIZED CONTAINERS OR ANY OTHER
POTENTIAL FIRE HAZARDOUS ARTICLES MUST NEVER BE PLACED ON
OR ADJACENT TO THE HEATER. OPEN CONTAINERS OF FLAMMABLE
MATERIAL SHOULD NOT BE STORED OR USED IN THE SAME ROOM WITH
THE HEATER.

When installing the heater, consideration must be given to proper location.
Location selected should be as close to the intake and exhaust termination
points as practicable, with adequate air supply and as centralized with the
piping system as possible.

THE HEATER MUST NOT BE LOCATED IN AN AREA WHERE IT WILL BE
SUBJECT TO FREEZING.

LOCATE IT NEAR A FLOOR DRAIN. THE HEATER SHOULD BE LOCATED IN
AN AREA WHERE LEAKAGE FROM THE HEATER OR CONNECTIONS WILL
NOT RESULT IN DAMAGE TO THE ADJACENT AREA OR TO LOWER FLOORS
OF THE STRUCTURE.

When such locations cannot be avoided, it is recommended that a suitable
drain pan, adequately drained, be installed under the appliance.

Water heater life depends upon water quality, water pressure and the
environment in which the water heater is installed. Water heaters are
sometimes installed in locations where leakage may result in property
damage, even with the use of a drain pan piped to a drain. However,
unanticipated damage can be reduced or prevented by a leak detector or
water shut-off device used in conjunction with a piped drain pan. These
devices are available from some plumbing supply wholesalers and retailers,
and detect and react to leakage in various ways:

• Sensors mounted in the drain pan that trigger an alarm or turn off the

incoming water to the water heater when leakage is detected.

• Sensors mounted in the drain pan that turn off the water supply to the

entire home when water is detected in the drain pan.

• Water supply shut-off devices that activate based on the water pressure

differential between the cold water and hot water pipes connected to
the water heater.

• Devices that will turn off the gas supply to a gas water heater while at

the same time shutting off its water supply.

 

WARNING

THIS WATER HEATER IS A CONDENSING UNIT AND REQUIRES A DRAIN TO
BE LOCATED IN CLOSE PROXIMITY TO ALLOW THE CONDENSATE TO
DRAIN SAFELY. THE CONDENSATE DRAINS FROM THE UNIT AT THE
EXHAUST ELBOW LOCATED AT THE BOTTOM OF THE UNIT. NOTE: IT IS
IMPORTANT THAT THE CONDENSATE HOSE NOT BE ELEVATED ABOVE
THE EXHAUST ELBOW (SEE FIGURE 3). THE CONDENSATE BUILD-UP WILL
BLOCK THE EXHAUST OUTLET, WHICH WILL CAUSE IMPROPER
OPERATION.

                

FIGURE 3

 

WARNING

DO NOT USE THIS APPLIANCE IF ANY PART HAS BEEN UNDER WATER.
IMMEDIATELY CALL A QUALIFIED SERVICE TECHNICIAN TO INSPECT THE
APPLIANCE AND TO REPLACE ANY PART OF THE CONTROL SYSTEM AND
ANY GAS CONTROL WHICH HAS BEEN UNDER WATER.

CLEARANCES

These heaters are approved for installation on combustible flooring in an
alcove when the minimum clearances from any combustion construction
are followed as indicated in Figure 4.

In all installations the minimum combustible clearances from any vent piping
shall be 0". Vent piping passing through a combustible wall or ceiling must
be a continuous run (no joints).

Содержание SUF 100 150NE

Страница 1: ...any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation...

Страница 2: ...SI Z21 10 3 CSA 4 3 as an automatic circulating tank water heater and automatic storage water heaters Detailed installation diagrams are found in this manual These diagrams will serve to provide the i...

Страница 3: ...ON 29 TROUBLESHOOTING 29 30 REPLACEMENTPARTS 30 LIMITED WARRANTY 31 FEATURES IMPORTANT ITIS REQUIREDTHATAQUALIFIED SERVICETECHNICIAN PERFORM THE INITIALFIRING OF THE HEATER ATTHIS TIME THE USER SHOULD...

Страница 4: ...MAN IN THE FIELD INVOLVED PLUMBING AIR SUPPLY VENTING GAS SUPPLY AND ELECTRICAL WORKARE REQUIRED INSULATION BLANKETS Insulation blankets available to the general public for external use on gas water h...

Страница 5: ...d it is recommended that a suitable drain pan adequately drained be installed under the appliance Water heater life depends upon water quality water pressure and the environment in which the water hea...

Страница 6: ...t system must terminate so that proper clearances are maintained as cited in local codes or the latest edition of the ANSI Z223 1 NFPA 54 1 Do not terminate the exhaust vent terminal over public area...

Страница 7: ...7 FIGURE 5 NOTE SUF 100 240 USES TEE ON AIR INTAKE TERMINAL DIRECT VENT HORIZONTAL VENT FIGURE 6...

Страница 8: ...y air inlet into building 4 The manufacturer also recommends the vent system terminations not be installed closer than 3 91cm from an inside corner of an L shaped structure And not less than 1 30 5 cm...

Страница 9: ...de of the line This will allow the vent pipe to easily slide through the opening The resulting gap will be covered by the vent terminal cover plates Repeat this step on the inside wall if necessary 4...

Страница 10: ...nt pipes to be inserted through the roof 2 Drill a pilot hole approximately 1 4 6 mm outside of the marked circle This pilot hole is used as a starting point for a saws all or sabre saw blade Cut arou...

Страница 11: ...ivalent feet 15 2 m of three inch PVC vent pipe on the intake Also verify that the intake and intake vent terminal is free of obstructions that may prevent air from entering the unit 3 4 inch PVC may...

Страница 12: ...HR FEET 1 2 3 4 1 1 1 4 1 1 2 2 2 1 2 3 4 10 175 360 680 1400 2100 3960 6300 11000 23000 20 120 250 485 950 1460 2750 4360 7700 15800 30 97 200 375 770 1180 2200 3520 6250 12800 40 82 170 320 660 990...

Страница 13: ...heater as well as the requirements of all other gas fired equipment supplied by the meter If the gas meter is too small ask the gas company to install a larger meter having adequate capacity GAS PRES...

Страница 14: ...WITH WATER NOTE This controller is Polarity Sensitive If the Hot and Neutral Supply Voltage is reversed the controller will not sense flame Verify polarity before connecting the unit WATER LINE CONNE...

Страница 15: ...tep 2 and repeat the entire operating cycle SELF DIAGNOSTIC CONTROLLER A green LED is mounted on the Main Control Board to indicate line voltage polarity is properly connected The green LED is mounted...

Страница 16: ...ame probe faulty 4 Replace flame probe 5 Gas shut off 5 Turn on gas supply 6 Clogged gas valve 6 Replace gas valve 7 Faulty gas valve 7 Replace gas valve 8 Defective control 8 Replace control 9 Burner...

Страница 17: ...trol problem 2 Water in tank above freezing 2 Temperature probe out of tolerance replace temp probe PossibleCause Remedy 1 Water in tank is low probe 1 Fill tank immersed in steam 2 Probe wiring short...

Страница 18: ...heck to ensure the unit is equipped with the correct orifice PRIOR TO START UP REQUIRED ABILITY INSTALLATION OR SERVICE OF THIS WATER HEATER REQUIRESABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN...

Страница 19: ...19 FORYOUR SAFETYREAD BEFORE OPERATING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life...

Страница 20: ...ING SUF HEATERSARE CERTIFIED FOR USE WITHOUT MODIFICATION FOR ALTITUDES UP TO 6500 FEET INSTALLATIONSABOVE 6500 FEET MAY REQUIREREPLACEMENTOFTHEBURNERORIFICE CALLTHETECHNICAL CENTER 800 527 1953 FOR R...

Страница 21: ...ished flushing 4 Turn on the heater electrical disconnect switch DRAINING The heater must be drained if it is to be shut down and exposed to freezing temperatures Maintenance and service procedures ma...

Страница 22: ...ration and a tank explosion In areas with poor water conditions it may be necessary to inspect the T P valve more often than every three years CAUTION BEFORE MANUALLY OPERATING THE VALVE MAKE SURE THA...

Страница 23: ...T WATER SUPPLIED TO FIXTURES PIPE TO OPEN DRAIN INSTALLINACCORDANCE WITH LOCAL CODES CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVEORWATERMETERWITH CHECK VALVE PROVISIONS...

Страница 24: ...R TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 3 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD...

Страница 25: ...KIT SPECIFICATIONS PAGE28 CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVE OR WATER METER WITH CHECK VALVE PROVISIONS FORTHERMALEXPANSION OF WATER IN THE HOT WATER SYSTEM MU...

Страница 26: ...ECTCIRCULATINGLINEOF180 F 82 C ORBOOSTEDWATER IF USED TO INLETWATER LINETO BOOSTER INSTALLINACCORDANCE WITH LOCALCODES TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR WITHOUT BUI...

Страница 27: ...HETANK NOTE4 IFTEMPEREDWATERISRECIRCULATED RETURNLINESHOULD BE CONNECTEDATPOINTA DANGER TEMPERATURESETTINGSHOULDNOTEXCEEDSAFETEMPERATUREAT FIXTURES SEE WATERTEMPERATURE CONTROLWARNING ON PAGE 3 IF HIG...

Страница 28: ...heating and storage potential of the system cannot be achieved Plus the units with the higher water flow may have a shortened life Unions shown in piping diagrams are not included in the manifold kit...

Страница 29: ...SUSPECTED 1 Check to see if the water heater drain valve is tightly closed Also check the cleanout opening for leakage 2 The apparent leakage may be condensation which forms on cool surfaces of the he...

Страница 30: ...5 kPa W C or lower than the minimal gas supply pressure as shown in Table 4 that is for Natural Gas 5 0 1 25 kPa W C for SUF 120 240 or 4 5 1 1 kPa W C for SUF 150 199 or for L P Gas 11 0 2 74 kPa W C...

Страница 31: ...31...

Страница 32: ...32 500 LIndahl Parkway Ashland City TN 37015 Phone 1 800 821 2017 Fax 1 800 644 9306 www stateind com...

Отзывы: