background image

29

CHECKLIST AND SERVICE INFORMATION

IMPORTANT

The installer may be able to observe and correct certain problems which
might arise when the unit is put into operation or when it is re-fired after a
prolonged shutdown. HOWEVER, it is recommended that only qualified
servicemen, using appropriate test equipment, be allowed to service the
heater.

BE SURE TO TURN OFF THE ELECTRICITY WHENEVER POSSIBLE OR
APPROPRIATE WHILE CHECKING EQUIPMENT.

 

WARNING

FAILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT IN SERIOUS
PERSONAL INJURY OR DEATH.

CAUTION:  LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING
CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS
OPERATION.

VERIFY PROPER OPERATION AFTER SERVICING.

BURNER OPERATIONAL PROBLEMS

  1. Refer to TROUBLESHOOTING.

NOT ENOUGH OR NO HOT WATER

1.

Be certain the electrical disconnect switch serving the water heater
is in the ON position.

2.

Check the fuses.

• The electrical  disconnect switch usually contains fuses.

3.

The capacity of the heater may have been exceeded by a large
demand for hot water.

• Large demands require a recovery period to restore water

temperature.

4.

Colder incoming water temperature will lengthen the time required to
heat water to the desired temperature.

• If the heater was installed when incoming water temperature was

warm, colder water creates the effect of less hot water.

5.

Look for hot water wastage and leaking or open hot water faucets.

6.

Sediment or lime scale may be affecting water heater operation.
Refer to MAINTENANCE for details.

7.

The heater’s temperature high limit sensor has activated. Press the
reset button on the thermostat.

8.

Burner may not be firing at proper rate.

• Check gas pressure. Adjust to obtain required manifold pressure.

9.

Burner fan wheel may be dirty.

• Clean fan wheel with a stiff brush.

10.

Condensate hose may be blocked where it connects to the exhaust
elbow.

• Verify the condensate drains from the unit without restriction.

WATER IS TOO HOT

1.

Refer to WATER TEMPERATURE CONTROL.

WATER HEATER MAKES SOUNDS

1.

Sediment or lime scale accumulations cause rumbling and pounding
noises when the heater is operating.

• The sounds are normal, however, the tank bottom should be cleaned.

Refer to MAINTENANCE for details.

2.

Some of the electrical components of the water heater make sounds
which are normal.

• Contacts click or snap as the heater starts and stops.
• Transformers often hum.

WATER LEAKAGE IS SUSPECTED

1.

Check to see if the water heater drain valve is tightly closed. Also
check the cleanout opening for leakage.

2.

The apparent leakage may be condensation which forms on cool
surfaces of the heater and piping.

3.

If the outlet of the relief valve is leaking it may represent:

• Excessive water pressure.
• Excessive water temperature.
• Faulty relief valve.

Excessive water pressure is the most common cause of relief valve
leakage. It is often caused by a “closed system”. If a check valve is in the
inlet system it will not permit the expanded hot water volume to equalize
pressure with the main. The relief valve must release this water or the
water heater or plumbing system will be damage d. Refer to MAINTENANCE-
RELIEF VALVE section in this manual.

When such a condition is encountered, local codes or inspection agency
should be consulted to determine which system is acceptable in your area.
See CLOSED SYSTEM section in this manual also.

TROUBLESHOOTING

1. Verify that the allowable vent length has not been exceeded and that the

blower inlet screen has been removed if direct venting.

2. Verify that the condensation, which WILL be present in the heater and

exhaust vent, will drain.

3. Check supply wire polarity - hot to hot and neutral to neutral and no

"stray" current in neutral.

4. Heater is properly grounded.

Checking these four (4) items first will often result in a timely solution to the
service call.

 

WARNING

JUMPING OUT COMPONENTS AND/OR CIRCUITS DURING
TROUBLESHOOTING CAN CAUSE SERIOUS PROBLEMS WITH THE UNIT’S
OPERATING SEQUENCE AND IGNITION SAFETY. IF YOU DO NOT HAVE THE
PROPER TEST EQUIPMENT, I.E. A VOLT-OHM METER AND A MICROAMMETER,
DO NOT ATTEMPT TO TROUBLESHOOT OR REPAIR A.O. SMITH EQUIPMENT.

ALTERING THE CONTROLLER AND/OR CONTROLLER WIRING IN ANY WAY
COULD RESULT IN INTERNAL DAMAGE TO THE MODULE CIRCUITS,
POSSIBLY ALTERING THE IGNITION SEQUENCE ALLOWING GAS VALVES
TO OPEN BEFORE THE HOT SURFACE IGNITER IS UP TO IGNITION
TEMPERATURE.

NOTE:  ANY BYPASS OR ALTERATION OF THE UNITS SAFETIES WILL
RESULT IN VOIDING THE APPLIANCE WARRANTY.

Before performing any troubleshooting familiarize yourself with the particular
appliance.

Refer to the SEQUENCE OF OPERATION and the connection diagram located
on page 15 before continuing.

Make sure the appliance is connected to a 120V AC power supply, manual
gas valve is in the ON position, and all electrical connections are secure
before continuing to troubleshoot this appliance.

 

CAUTION

THE WATER HEATER IS POLARITY SENSITIVE. BEFORE APPLYING
ELECTRICITY TO THIS HEATER BE CERTAIN THAT SUPPLY HEATED WIRE
TO GROUND CHECK INDICATES ZERO VOLTAGE.

Содержание SUF 100 150NE

Страница 1: ...any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation...

Страница 2: ...SI Z21 10 3 CSA 4 3 as an automatic circulating tank water heater and automatic storage water heaters Detailed installation diagrams are found in this manual These diagrams will serve to provide the i...

Страница 3: ...ON 29 TROUBLESHOOTING 29 30 REPLACEMENTPARTS 30 LIMITED WARRANTY 31 FEATURES IMPORTANT ITIS REQUIREDTHATAQUALIFIED SERVICETECHNICIAN PERFORM THE INITIALFIRING OF THE HEATER ATTHIS TIME THE USER SHOULD...

Страница 4: ...MAN IN THE FIELD INVOLVED PLUMBING AIR SUPPLY VENTING GAS SUPPLY AND ELECTRICAL WORKARE REQUIRED INSULATION BLANKETS Insulation blankets available to the general public for external use on gas water h...

Страница 5: ...d it is recommended that a suitable drain pan adequately drained be installed under the appliance Water heater life depends upon water quality water pressure and the environment in which the water hea...

Страница 6: ...t system must terminate so that proper clearances are maintained as cited in local codes or the latest edition of the ANSI Z223 1 NFPA 54 1 Do not terminate the exhaust vent terminal over public area...

Страница 7: ...7 FIGURE 5 NOTE SUF 100 240 USES TEE ON AIR INTAKE TERMINAL DIRECT VENT HORIZONTAL VENT FIGURE 6...

Страница 8: ...y air inlet into building 4 The manufacturer also recommends the vent system terminations not be installed closer than 3 91cm from an inside corner of an L shaped structure And not less than 1 30 5 cm...

Страница 9: ...de of the line This will allow the vent pipe to easily slide through the opening The resulting gap will be covered by the vent terminal cover plates Repeat this step on the inside wall if necessary 4...

Страница 10: ...nt pipes to be inserted through the roof 2 Drill a pilot hole approximately 1 4 6 mm outside of the marked circle This pilot hole is used as a starting point for a saws all or sabre saw blade Cut arou...

Страница 11: ...ivalent feet 15 2 m of three inch PVC vent pipe on the intake Also verify that the intake and intake vent terminal is free of obstructions that may prevent air from entering the unit 3 4 inch PVC may...

Страница 12: ...HR FEET 1 2 3 4 1 1 1 4 1 1 2 2 2 1 2 3 4 10 175 360 680 1400 2100 3960 6300 11000 23000 20 120 250 485 950 1460 2750 4360 7700 15800 30 97 200 375 770 1180 2200 3520 6250 12800 40 82 170 320 660 990...

Страница 13: ...heater as well as the requirements of all other gas fired equipment supplied by the meter If the gas meter is too small ask the gas company to install a larger meter having adequate capacity GAS PRES...

Страница 14: ...WITH WATER NOTE This controller is Polarity Sensitive If the Hot and Neutral Supply Voltage is reversed the controller will not sense flame Verify polarity before connecting the unit WATER LINE CONNE...

Страница 15: ...tep 2 and repeat the entire operating cycle SELF DIAGNOSTIC CONTROLLER A green LED is mounted on the Main Control Board to indicate line voltage polarity is properly connected The green LED is mounted...

Страница 16: ...ame probe faulty 4 Replace flame probe 5 Gas shut off 5 Turn on gas supply 6 Clogged gas valve 6 Replace gas valve 7 Faulty gas valve 7 Replace gas valve 8 Defective control 8 Replace control 9 Burner...

Страница 17: ...trol problem 2 Water in tank above freezing 2 Temperature probe out of tolerance replace temp probe PossibleCause Remedy 1 Water in tank is low probe 1 Fill tank immersed in steam 2 Probe wiring short...

Страница 18: ...heck to ensure the unit is equipped with the correct orifice PRIOR TO START UP REQUIRED ABILITY INSTALLATION OR SERVICE OF THIS WATER HEATER REQUIRESABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN...

Страница 19: ...19 FORYOUR SAFETYREAD BEFORE OPERATING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life...

Страница 20: ...ING SUF HEATERSARE CERTIFIED FOR USE WITHOUT MODIFICATION FOR ALTITUDES UP TO 6500 FEET INSTALLATIONSABOVE 6500 FEET MAY REQUIREREPLACEMENTOFTHEBURNERORIFICE CALLTHETECHNICAL CENTER 800 527 1953 FOR R...

Страница 21: ...ished flushing 4 Turn on the heater electrical disconnect switch DRAINING The heater must be drained if it is to be shut down and exposed to freezing temperatures Maintenance and service procedures ma...

Страница 22: ...ration and a tank explosion In areas with poor water conditions it may be necessary to inspect the T P valve more often than every three years CAUTION BEFORE MANUALLY OPERATING THE VALVE MAKE SURE THA...

Страница 23: ...T WATER SUPPLIED TO FIXTURES PIPE TO OPEN DRAIN INSTALLINACCORDANCE WITH LOCAL CODES CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVEORWATERMETERWITH CHECK VALVE PROVISIONS...

Страница 24: ...R TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 3 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD...

Страница 25: ...KIT SPECIFICATIONS PAGE28 CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVE OR WATER METER WITH CHECK VALVE PROVISIONS FORTHERMALEXPANSION OF WATER IN THE HOT WATER SYSTEM MU...

Страница 26: ...ECTCIRCULATINGLINEOF180 F 82 C ORBOOSTEDWATER IF USED TO INLETWATER LINETO BOOSTER INSTALLINACCORDANCE WITH LOCALCODES TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR WITHOUT BUI...

Страница 27: ...HETANK NOTE4 IFTEMPEREDWATERISRECIRCULATED RETURNLINESHOULD BE CONNECTEDATPOINTA DANGER TEMPERATURESETTINGSHOULDNOTEXCEEDSAFETEMPERATUREAT FIXTURES SEE WATERTEMPERATURE CONTROLWARNING ON PAGE 3 IF HIG...

Страница 28: ...heating and storage potential of the system cannot be achieved Plus the units with the higher water flow may have a shortened life Unions shown in piping diagrams are not included in the manifold kit...

Страница 29: ...SUSPECTED 1 Check to see if the water heater drain valve is tightly closed Also check the cleanout opening for leakage 2 The apparent leakage may be condensation which forms on cool surfaces of the he...

Страница 30: ...5 kPa W C or lower than the minimal gas supply pressure as shown in Table 4 that is for Natural Gas 5 0 1 25 kPa W C for SUF 120 240 or 4 5 1 1 kPa W C for SUF 150 199 or for L P Gas 11 0 2 74 kPa W C...

Страница 31: ...31...

Страница 32: ...32 500 LIndahl Parkway Ashland City TN 37015 Phone 1 800 821 2017 Fax 1 800 644 9306 www stateind com...

Отзывы: