background image

30

MOTOR WILL NOT RUN

1. Confirm 120V AC to the controller. Also, to verify correct polarity, check

for 120 V AC between hot supply and ground.

If there is no voltage, check for a loose connection where it connects to
the controller.

2. If there is 120 volts to the controller, check for loose connections or a

locked rotor. If the rotor cannot be freed the motor and blower assembly
must be replaced.

MOTOR RUNS, PREPURGE TIME ELAPSES BUT MAIN

FLAME NOT ESTABLISHED.

1. Check to see if main manual gas valve is open.

2. Check for a loose connection at the transformer, or a defective

transformer.

3. Check for a loose connection at the gas valve.

4. Check for open pressure switches or open reset button. Check for

blockage in the intake and exhaust venting or at the vent hoods. If no
blockage is found, check vinyl tubing for cuts or crimps. If this tubing is
damaged it must be replaced. If these steps do not eliminate the problem,
replace the pressure switches.

5. Check to see if there is resistance across the igniter terminal with an

OHM meter. If there is no continuity, the igniter is broken and should be
replaced.

If the igniter appears to function properly, then verify that the inlet
pressure is 12" Natural Gas (3 kPa) and 14.0" L.P. Gas (3.45 kPa) W.C.
maximum. The gas valve supplied on this appliance is not designed to
open against a higher pressure. At this time also check that the inlet
pressure is not lower than the minimal gas supply pressure, as shown
in Table 4: that is, for Natural Gas, 5.0" (1.25 kPa) W.C. for SUF 120 &
240 or 4.5"  (1.1 kPa) W.C. for SUF 150 & 199 or; for L.P. Gas, 11.0"
(2.74 kPa) W.C. if the inlet pressure is not within these limits then adjust
the supply pressure accordingly.

If the inlet pressure falls within the allowable limits, then verify that the
manifold pressure, when the gas is fully open, with the heater running,
is as called out in Table 4:  that is, for Natural Gas, 4.0" (1 kPa)  W.C. for
SUF 120 & 240 or 3.5" (.9 kPa)  W.C. for SUF 150 & 199 or; for L.P. Gas,
10.0"  (2.5 kPa) W.C. If the manifold pressure is not correct then adjust
accordingly.  See ADJUSTMENT PROCEDURE in OPERATING
INSTRUCTIONS selection, page 18, for the manifold pressure adjustment
procedure.

6. If the inlet and manifold pressures are within the limits specified in step

5, then reset the appliance. Verify 24V AC at the gas valve during the
three (3) second ignition trial, after the igniter reaches operating
temperature. If 24V AC at the gas valve is not seen during this period,
the controller must be replaced.

If there is 24V AC at the gas valve during the four second ignition trial
and the manifold pressure does not increase above 0" W.C. then verify
that the manual gas control valve is in the “ON” position (see page 20).
If the valve is in the “ON” position and the previous voltage and gas
pressure conditions are met, then the gas valve is defective and must
be replaced.

Note that a positive manifold pressure reading of approximately
1.5" (.38 kPa) W.C. is normal during the prepurge portion of the ignition
cycle due to the location of the gas orifice.

MOTOR RUNS, BURNER LIGHTS MOMENTARILY,

THEN LOCKS OUT

1. Reset the appliance two more times to ensure that all of the air has been

purged from the gas line.

2. If the burner lights momentarily but does not sustain ignition, verify that

the inlet pressure is not greater than 14.0" (3.5 kPa) W.C. or lower than

the minimal gas supply pressure, as shown in Table 4: that is, for
Natural Gas, 5.0" (1.25 kPa) W.C. for SUF 120 & 240 or 4.5" (1.1 kPa)
W.C. for SUF 150 & 199 or; for L.P. Gas, 11.0" (2.74 kPa) W.C. pressure.
Also, the manifold pressure should rise during the three (3) second trial
for ignition to the manifold pressure value for the individual unit listed in
Table 4: that is, for Natural Gas, 4.0" (1 kPa) W.C. for SUF 120 & 240 or
3.5" (.9 kPa) W.C. for SUF 150 & 199 or; for L.P. Gas, 10.0" (2.5 kPa)
W.C. If the manifold pressure is not correct then adjust accordingly. See
ADJUSTMENT PROCEDURE in OPERATING INSTRUCTIONS section, page
18, for the manifold pressure adjustment procedure.

3. Check for the reversed polarity in the supply wiring. This controller is

polarity sensitive. If the hot and neutral supply wires are reversed, the
controller will not sense flame. Reverse the supply wires and try to fire
the unit.

NOTE:  

Always turn off and disconnect main supply wiring before servicing

the unit.

4. Check connecting wire to the flame sensor. Verify that the flame sensor

has not been damaged in any way.

5. Verify that the air supply is adequate. The air inlet screen or blower

wheel may be restricted. Also, check the installation for proper ventilation.
See AIR REQUIREMENTS.

6. Check the venting system for the correct sizing, excess or insufficient.

See VENTING.

7. Check for a maximum inlet pressure of 12" Natural Gas (3 kPa), 14.0"

L.P. Gas (3.45 kPa) W.C. and the manifold pressure as listed in Table 4:
that is, for Natural Gas, 4.0" (1 kPa) W.C. for SUF 120 & 240 or 3.5" (.9
kPa) W.C. for SUF 150 & 199 or; for L.P. Gas, 10.0" (2.5 kPa) W.C.
Please note that the manifold pressure listed is the maximum value for
the manifold pressure. Do not set the manifold pressure higher than the
value shown for your heater in Table 4. Overfiring the heater will result
in rough ignition and/or noisy operation.

8. Confirm that the air inlet screen (see Figures 7 & 8) is free of obstructions.

 

 

CAUTION

Do not reach into the burner housing or combustion chamber if the heater
is still hot. Allow the heater to cool and always use gloves as the combustion
chamber and the burner sleeve and housing can become very hot after
operation. Overfiring is a dangerous condition that must be corrected
immediately.

NOISY BURNER OPERATION

The exhaust of this unit produces some noise. This noise may be
objectionable if the exhaust terminal is located too close to the opening of
an occupied space. The noise may also be objectionable if the exhaust is
located in the confined space between two buildings such as an alley or
walkway. Since everyone's perception and tolerance for background noise
varies, there is no standard recommendation. The best option when the
noise is a concern is to locate the exhaust as far away from any occupied
spaces as practical.

If noise becomes more than one can tolerate, a dampening muffler is available
through our Product Service Division. See “REPLACEMENT PARTS” segment
below.

GAS FAILS TO SHUT OFF

Check for defective gas valve or thermostat. If operation is incorrect,
replace.

REPLACEMENT PARTS

Replacement parts may be ordered through State dealers, authorized
servicers or distributors. Refer to the Yellow Pages for where to call or
contact the State Water Heaters, 500 Lindahl Parkway, Ashland City, TN
37015, 1-800-821-2017. When ordering parts be sure to state the quantity,
part number and description of the items including the complete model and
serial number as it appears on the product. Refer to the parts list for more
information.

Содержание SUF 100 150NE

Страница 1: ...any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation...

Страница 2: ...SI Z21 10 3 CSA 4 3 as an automatic circulating tank water heater and automatic storage water heaters Detailed installation diagrams are found in this manual These diagrams will serve to provide the i...

Страница 3: ...ON 29 TROUBLESHOOTING 29 30 REPLACEMENTPARTS 30 LIMITED WARRANTY 31 FEATURES IMPORTANT ITIS REQUIREDTHATAQUALIFIED SERVICETECHNICIAN PERFORM THE INITIALFIRING OF THE HEATER ATTHIS TIME THE USER SHOULD...

Страница 4: ...MAN IN THE FIELD INVOLVED PLUMBING AIR SUPPLY VENTING GAS SUPPLY AND ELECTRICAL WORKARE REQUIRED INSULATION BLANKETS Insulation blankets available to the general public for external use on gas water h...

Страница 5: ...d it is recommended that a suitable drain pan adequately drained be installed under the appliance Water heater life depends upon water quality water pressure and the environment in which the water hea...

Страница 6: ...t system must terminate so that proper clearances are maintained as cited in local codes or the latest edition of the ANSI Z223 1 NFPA 54 1 Do not terminate the exhaust vent terminal over public area...

Страница 7: ...7 FIGURE 5 NOTE SUF 100 240 USES TEE ON AIR INTAKE TERMINAL DIRECT VENT HORIZONTAL VENT FIGURE 6...

Страница 8: ...y air inlet into building 4 The manufacturer also recommends the vent system terminations not be installed closer than 3 91cm from an inside corner of an L shaped structure And not less than 1 30 5 cm...

Страница 9: ...de of the line This will allow the vent pipe to easily slide through the opening The resulting gap will be covered by the vent terminal cover plates Repeat this step on the inside wall if necessary 4...

Страница 10: ...nt pipes to be inserted through the roof 2 Drill a pilot hole approximately 1 4 6 mm outside of the marked circle This pilot hole is used as a starting point for a saws all or sabre saw blade Cut arou...

Страница 11: ...ivalent feet 15 2 m of three inch PVC vent pipe on the intake Also verify that the intake and intake vent terminal is free of obstructions that may prevent air from entering the unit 3 4 inch PVC may...

Страница 12: ...HR FEET 1 2 3 4 1 1 1 4 1 1 2 2 2 1 2 3 4 10 175 360 680 1400 2100 3960 6300 11000 23000 20 120 250 485 950 1460 2750 4360 7700 15800 30 97 200 375 770 1180 2200 3520 6250 12800 40 82 170 320 660 990...

Страница 13: ...heater as well as the requirements of all other gas fired equipment supplied by the meter If the gas meter is too small ask the gas company to install a larger meter having adequate capacity GAS PRES...

Страница 14: ...WITH WATER NOTE This controller is Polarity Sensitive If the Hot and Neutral Supply Voltage is reversed the controller will not sense flame Verify polarity before connecting the unit WATER LINE CONNE...

Страница 15: ...tep 2 and repeat the entire operating cycle SELF DIAGNOSTIC CONTROLLER A green LED is mounted on the Main Control Board to indicate line voltage polarity is properly connected The green LED is mounted...

Страница 16: ...ame probe faulty 4 Replace flame probe 5 Gas shut off 5 Turn on gas supply 6 Clogged gas valve 6 Replace gas valve 7 Faulty gas valve 7 Replace gas valve 8 Defective control 8 Replace control 9 Burner...

Страница 17: ...trol problem 2 Water in tank above freezing 2 Temperature probe out of tolerance replace temp probe PossibleCause Remedy 1 Water in tank is low probe 1 Fill tank immersed in steam 2 Probe wiring short...

Страница 18: ...heck to ensure the unit is equipped with the correct orifice PRIOR TO START UP REQUIRED ABILITY INSTALLATION OR SERVICE OF THIS WATER HEATER REQUIRESABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN...

Страница 19: ...19 FORYOUR SAFETYREAD BEFORE OPERATING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life...

Страница 20: ...ING SUF HEATERSARE CERTIFIED FOR USE WITHOUT MODIFICATION FOR ALTITUDES UP TO 6500 FEET INSTALLATIONSABOVE 6500 FEET MAY REQUIREREPLACEMENTOFTHEBURNERORIFICE CALLTHETECHNICAL CENTER 800 527 1953 FOR R...

Страница 21: ...ished flushing 4 Turn on the heater electrical disconnect switch DRAINING The heater must be drained if it is to be shut down and exposed to freezing temperatures Maintenance and service procedures ma...

Страница 22: ...ration and a tank explosion In areas with poor water conditions it may be necessary to inspect the T P valve more often than every three years CAUTION BEFORE MANUALLY OPERATING THE VALVE MAKE SURE THA...

Страница 23: ...T WATER SUPPLIED TO FIXTURES PIPE TO OPEN DRAIN INSTALLINACCORDANCE WITH LOCAL CODES CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVEORWATERMETERWITH CHECK VALVE PROVISIONS...

Страница 24: ...R TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 3 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD...

Страница 25: ...KIT SPECIFICATIONS PAGE28 CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVE OR WATER METER WITH CHECK VALVE PROVISIONS FORTHERMALEXPANSION OF WATER IN THE HOT WATER SYSTEM MU...

Страница 26: ...ECTCIRCULATINGLINEOF180 F 82 C ORBOOSTEDWATER IF USED TO INLETWATER LINETO BOOSTER INSTALLINACCORDANCE WITH LOCALCODES TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR WITHOUT BUI...

Страница 27: ...HETANK NOTE4 IFTEMPEREDWATERISRECIRCULATED RETURNLINESHOULD BE CONNECTEDATPOINTA DANGER TEMPERATURESETTINGSHOULDNOTEXCEEDSAFETEMPERATUREAT FIXTURES SEE WATERTEMPERATURE CONTROLWARNING ON PAGE 3 IF HIG...

Страница 28: ...heating and storage potential of the system cannot be achieved Plus the units with the higher water flow may have a shortened life Unions shown in piping diagrams are not included in the manifold kit...

Страница 29: ...SUSPECTED 1 Check to see if the water heater drain valve is tightly closed Also check the cleanout opening for leakage 2 The apparent leakage may be condensation which forms on cool surfaces of the he...

Страница 30: ...5 kPa W C or lower than the minimal gas supply pressure as shown in Table 4 that is for Natural Gas 5 0 1 25 kPa W C for SUF 120 240 or 4 5 1 1 kPa W C for SUF 150 199 or for L P Gas 11 0 2 74 kPa W C...

Страница 31: ...31...

Страница 32: ...32 500 LIndahl Parkway Ashland City TN 37015 Phone 1 800 821 2017 Fax 1 800 644 9306 www stateind com...

Отзывы: