APPENDIX-1 GENERAL FAULT AND THEIR SOLUTIONS
1. INVERTER OUTPUT VOLTAGE IS NOT AVAILABLE
CAUSE
REMEDY
Input DC Voltage is not available
Make it available first
MCB switch is kept in OFF position
Check the position of MCB and keep it at ON position
Battery connected in reverse polarity
Check the position of ON/OFF switch and keep it at ON position
System is trip DC under voltage condition
Assure input DC range is above the DC under voltage cut setting
2. SOLAR CHARGING IS NOT AVAILABLE
CAUSE
REMEDY
PV voltage is not available
Make it available first
PV MCB switch is kept in OFF position
Check the position of PV MCB and keep it at ON position
ON/OFF switch is kept in OFF position
Check the position of ON/OFF switch and keep it at ON position
PV is connected in reverse polarity
Check the PV connection polarity
Check the input PV range is within the
specified range
Input PV range should be within the specified range
3. MAINS CHARGING IS NOT HAPPENING
CAUSE
REMEDY
Mains MCB switch is kept in OFF position
Check the position of mains MCB and keep it at ON position
ON/OFF switch is kept in OFF position
Check the position of ON/OFF switch and keep it at ON position
Relay and contactors may be faulty
Check relay and contactors are operated
Mains voltage is not available
Make it available first
4. OUTPUT FLUCTUATION
CAUSE
REMEDY
Inappropriate connection of output terminal
Tightly and correctly connect the output terminals