iQ Control Box
6 Document # 204143 REV 5 • www.stanleyaccess.com • 1.800.7.ACCESS
Cop
yr
ight 2019, S
tanley Ac
cess T
echnologies, LL
C. All rights r
es
er
ved. R
epr
oduction
in whole or in p
ar
t without the expr
ess wr
itt
en permission o
f S
tanley is pr
ohibit
ed.
10.18.2019
WIRING INSTRUCTIONS
Evaluate Power Requirements
EVALUATE door system power requirements as follows:
• ENSURE power source is a dedicated 115 VAC, 50/60 Hz source with 20A circuit rating per two controllers.
• ENSURE power source is not shared with other equipment, i.e., cash registers, EAS systems, or other
electromagnetic interference generators.
Connecting Main Power Wiring
Warning
:
To prevent injury to personnel, incoming electrical power to header must be de-energized before
connecting control box electrical harness to electrical service.
• DE-ENERGIZE incoming electrical power to header.
• Refer to Attachments 2, 3, and 4, and using the wire nut provided, CONNECT ground wire assembly (P/N
711527) to electrical service ground wire.
• In a concealed location inside the header (not visible from the exterior of the header), DRILL a hole for a
No. 8 screw.
• INSTALL ground wire ring terminal and star washer onto the No. 8 screw provided, and FASTEN screw, star
washer, and ground wire to header.
• In a concealed location inside the header, DRILL a second hole for a No. 8 screw.
• INSTALL power line harness 412544 ring terminal and star washer onto the No. 8 screw provided, and FASTEN
screw, star washer, and ground wire to header.
• Using the wire nuts provided, CONNECT power line harness 412544 to electrical service as follows:
• CONNECT power pigtail assembly black wire to black (line) service wire.
• CONNECT power pigtail assembly white wire to white (neutral) service wire.
Connecting Breakout Status Signal Wiring (Magic-Swing Operators)
Warning
: To prevent injury to personnel and damage to equipment, control box power must be de-energized
before connecting breakout status signal wiring.
Caution
: If the motor is running and the breakout status switch is
not
connected, arcing across the breakout
switch contacts can occur. This will result in damage to the breakout switch. To prevent damage from switch
contact arcing, the breakout status switch must
always
be connected.
NOTES
:
The breakout status switch must be used in all applications where there is no positive door stop in the
breakout direction.
The auxiliary switch is the breakout status signal switch. The auxiliary switch was formerly the open check switch
on the operator switch plate (top cam).
• Refer to Attachment 1, and CONNECT breakout status wiring.
• REMOVE quick-connect terminal (brown wire) from the normally open terminal of the auxiliary switch
(formerly open check switch), and INSTALL onto normally closed terminal.