Control valves, I/P converters, Indicators, etc. without or with HART
communication for use in
Nonhazardous, Class I, II, III, Division 2, Group A-G
or Class I, Zone 2, Group IIC/IIB
Hazardous (Classified) Locations
Wiring legend
Connection allocation – Analog Output Module Type 9465
Channel
number
Function
2-wire i/p
converter
Connection X1
Terminal no.
0
Input (+) / Input (-)
1 / 2
1
Input (+) / Input (-)
3 / 4
2
Input (+) / Input (-)
5 / 6
3
Input (+) / Input (-)
7 / 8
4
Input (+) / Input (-)
9 / 10
5
Input (+) / Input (-)
11 / 12
6
Input (+) / Input (-)
13 / 14
7
Input (+) / Input (-)
15 / 16
The Analog Output Module Type 9465/15-08-12 and the Analog
Output Module HART Type 9466/15-08-12 are designed to receive a
binary output from the IS1 CPU & Power and output a corresponding
analog signal to positioners, loop distance, etc..
The modules are associated apparatus for use in Nonhazardous,
Class I, Division 2, Group A-D or Class I, Zone 2, Group IIC
Hazardous (Classified) Locations according to NEC Article 504/505.
Type 9465/15-08-12 and Type 9466/15-08-12
The internal system circuits are safely galvanically isolated from all
input circuits up to a peak voltage of 375 V.
Maximum Safety Voltage for the Input circuits: U
max
= 253 V AC
Entity parameters for the input circuits in type of protection AEx nL are
as follows:
9465/15-08-12
9466/15-08-12
V
OC
/ I
SC
/ P
O
[V / mA / mW]
V
max
/ I
max
/ C
i
/ L
i
[V / mA / nF / mH]
linear current limitation
non-linear limitation
23.8 / 113 / 553
23.8 / 36 / 567
32 / any / 1.2 / 0
Co and Lo values based on the non-linear current limitation
Lo (La) [mH]
Co (Ca) [µF]
CL I, DIV 2, A, B / Zone 2, GP IIC
2.0
0.466
CL I, DIV 2, C-G / Zone 2, GP IIB/IIIC
20
2.78
CL I, DIV 2, D / Zone 2, GP IIA
100
11.2
Notes:
1.
For connection of AEx nL circuits per Entity concept use the
appropriate parameters from above to ensure the following:
V
OC
or V
t
V
max
C
a
C
i
+ C
leads
I
SC
or I
t
I
max
L
a
L
i
+ L
leads
2.
Suitable separation must be maintained between non I.S. / AEx
nL wiring of the input circuits and I.S. wiring of other I/O modules
and of the IS1 resp. IS1+ system. Use partition (SAP No. 162740)
for separation from I/O modules with I.S. circuits. Do not carry out
work at the terminals without the partition plate in place.
3.
Electrical Apparatus connected to an intrinsically safe system
must not use or generate voltages > 250 V (U
max
)
4.
Connect either non I.S. circuits or AEx nL circuits. Do not mix
different types of circuits.
5.
Do not disconnect Non-I.S. field wiring unless area is known to be
non hazardous. Mechanically secure the terminal blocks with the
screws provided, to prevent from being detached unintentionally.
6.
If connecting AEx nL circuits attach the enclosed marking to the
to the detachable terminal block to allow for plug and unplug the
terminals even in hazardous areas.
7.
Only use BusRail extension Type 9494/L1-V* fitted aside the
module. Do not mount the module fitted aside BusRail Begin or
BusRail Begin types 9494/A2-B0 or 9494/A2-E0.
8.
Connecting the module even at one single point to a non-
intrinsically safe circuit cancels the AEx nL type of protection.
9.
General Notes (see Page 1)
WARNING:
Substitution of components may impair Intrinsic Safety.
AVERTISSEMENT:
Substitution de composants peut compromettre la sécurité intrinsèque.
Analog Output Module (HART)
Type 9465/15-08-12 and 9466/15-08-12