 IS1 I/O-Modules

Analog Output Module HART for Installation in Zone 2 Type 9466/15

3

S-BA-9466/15-08-12-0

-en-

/1

/20

 162468 / 9466602310

www.stahl.de

Operating Instructions for the IS1-System

If non-energy limited electric circuits are connected to a 
module, then it is allowed to operate the module in Zone 2 
only if de-energised or for maintenance purposes while 
considering IEC/EN 60079-17 Part 4.6. The plug-in terminal 
X1 for the input electric circuits must be secured against 
loosening by means of a gland.

The screens on the fieldbus cabling must be connected to the 
equipotential bonding system of the hazardous area! For this 
purpose the screens on the fieldbus cabling must be 
connected to the screen bars installed in the enclosures as 
close as possible to the entry point! The screen bars must 
also be connected to the mounting plate close to the entry 
points for the fieldbus cabling by the shortest possible route!

Assembly and Installation

Marking of the plug-in terminal X1

When connecting the Ex nL electric circuit cover the yellow 
warning sign 

 on the terminal with the sign enclosed to the 

module with Ex nL marking.

The sign with type specification 

 enclosed to the module 

must be placed on the terminal according to the drawing 
under the warning sign.

Assembly on the BusRail

Connect the field devices to the plug-in terminal X1.

If necessary, place the Ex nL marking onto the terminal.

Connect screens on the fieldbus cabling to earth bars as 
close as possible to the entry point.

Position the module vertically at the intended slot of the 
BusRail.

Engage the module by slightly pressing it.

If necessary, engage the partition between the modules.

Plug in the plug-in terminal X1 into the module and secure it 
by means of screws against loosening.

Replacing the Module

Before working on non-enery limited electric circuits ensure 
that they are de-energised!

Loosen the screws of the plug-in terminal X1.

Pull out the terminal from the module.

If necessary, remove the partition.

Pull the red detent lever of the module upwards to unlock the 
module.

Remove the module vertically from the BusRail.

Position the new module vertically onto the BusRail and 
engage it by slightly pressing it.

If necessary, engage the partition between the modules.

Plug in the plug-in terminal X1 into the module and secure it 
by means of screws against loosening.

Maintenance and Servicing

The module is maintenance-free.
Observe the function according to its designated use.
Adhere to the directives according to IEC/EN 60079-17.
Adhere to the permissible temperatures according to 
IEC/EN 60079-0.

Repair

For repair send the module to the responsible sales organisation 
(address see www.stahl.de).
Repair work is only to be performed by the manufacturer.

Transport and Storage

Transport and storage are only permitted in the original packing.

Disposal

The national installation instructions 
(e.g. IEC/EN 60079-14) must be observed.
Intrinsically-safe and non-intrinsically safe circuits must 
not be used in a common conduit!
Ensure that there is a distance of at least 50 mm left 
between the connection parts of intrinsically-safe and 
non-intrinsically safe circuits!

Assemble a partition (ID-No.: 162740) before 
assembling the module near a Zone 1 module (94../.2)!

Performing any work on non-energy limited electric 
circuits in a hazardous area is allowed only if de-
energised. The plug-in terminal X1 must be secured 
against loosening by means of a gland.

The screens on the fieldbus cabling must be connected 
to the equipotential bonding system of the hazardous 
area!
For this purpose the screens on the fieldbus cabling 
must be connected to the screen bars installed in the 
enclosures as close as possible to the entry point!
The screen bars must also be connected to the 
mounting plate close to the entry points for the fieldbus 
cabling by the shortest possible route!

The module and plug-in terminal X1 can be safely 
connected or disconnected during operation in 
potentially explosive area (hot swap).
In energy-limited electric circuits the plug-in terminal 
can be safely plugged in or pulled out during operation 
in the hazardous area.

Risk of confusion!
The plug-in terminal X1 must be marked in accordance 
with the connected electric circuits.

Spring clamp terminal
ID-No.: 162710

Screw terminal
ID-No.: 162708

05684E00

2

1

1

2

A connection diagram is imprinted on the rear side of 
the symbol label at the protective cover.

Operation of the module is permissible only in the 
following assembly positions:
Vertical assembly with a plug-in terminal below, on the 
left or right.

Before working on non-enery limited electric circuits 
ensure that they are de-energised!

Before removing the partition between the module and 
a Zone 1 module the plug-in terminal X1 must be pulled 
out of the module to be replaced!

When replacing the module with a module identical in 
construction the previous parameters are applied. No 
further settings are necessary.
When replacing the module by another module it is 
identified correctly at the slot, since the previously set 
parameters do not suit this module, it reports a 
configuration fault. The module must be either 
parameterised again or it is necessary to connect the 
module of the right type.

Observe the national standard for refuse disposal.

Содержание IS1 9466/15

Страница 1: ...fheben k nnen dass das Analog Output Modul HART Typ 9466 15 08 12 nur f r den Einsatz in explosionsgef hrdeten Bereichen der Zone 2 oder im sicheren Bereich zugelassen ist dass das Modul bei Einsatz i...

Страница 2: ...rte der angeschlossenen Feldger te zu den H chstwerten der Modul Ausg nge passen Nach IEC EN 60079 15 gilt Ui Uo li Io Pi Po Ci Ccable Co Li Lcable Lo Nach Anschluss des Moduls an einen nicht energieb...

Страница 3: ...ern sichern Wartung und Instandhaltung Das Modul ist wartungsfrei Beachten Sie die bestimmungsgem e Funktion Halten Sie sich an die Richtlinien nach IEC EN 60079 17 Halten Sie die zul ssigen Temperatu...

Страница 4: ...g nge in Sicherheitsstellung Zyklischer Datenverkehr mit dem Master ist unterbrochen Zyklischen Datenverkehr mit dem Master in Betrieb setzen Master Busverbindung und CPM pr fen Blinkt Ein Konfigurati...

Страница 5: ...ngen 5ms Messgenauigkeit Hinweis Alle Angaben in der Signalspanne bei 23 C Messabweichung 0 06 Einfluss der Umgebungstemperatur 0 06 10 K MTBF nach MIL 31 1 Jahre bei 40 C Einstellungen Drahtbruch Kur...

Страница 6: ...eratur 40 C 70 C Maximale relative Feuchte 95 keine Betauung Vibration sinusf rmig IEC EN 60068 2 6 1 g im Frequenzbereich 10 500 Hz 2 g im Frequenzbereich 45 100 Hz Schock halbsinusf rmig IEC EN 6006...

Страница 7: ...signale Beschriftung 1 16 162708 09899E00 Federkraftanschluss 2 5 mm2 mit Arretierung und Pr fbuchsen 16 polig schwarz zum Anschluss Ex nL Ex nA Feldsignale Beschriftung 1 16 162710 Beschriftungsstrei...

Страница 8: ...ial conditions contained in it that any damage may render explosion protection null and void that the Analog Output Module HART of type 9466 15 08 12 is certified for application in hazardous areas of...

Страница 9: ...C EN 60079 15 the following applies Ui Uo li Io Pi Po Ci Ccable Co Li Lcable Lo After the module has been connected to a non energy limited electric circuit the feature Ex nL of the module is no longe...

Страница 10: ...o the permissible temperatures according to IEC EN 60079 0 Repair For repair send the module to the responsible sales organisation address see www stahl de Repair work is only to be performed by the m...

Страница 11: ...onnected Change configuration of master or connect the right module Off On or blinks I O module hardware fault Hardware check fault Eprom fault EEprom fault Replace the I O module Off Off Off No suppl...

Страница 12: ...onitoring ON OFF for each channel Safety position Output safety position during communication faults 10 0 100 110 of signal hold last value parameterizable Stop time to safety position 0 1 2 254 255 x...

Страница 13: ...o condensation Vibration sinusoidal IEC EN 60068 2 6 1 g in the frequency range between 10 500 Hz 2 g in the frequency range between 45 100 Hz Semi sinusoidal shock IEC EN 60068 2 27 15 g 3 shocks per...

Страница 14: ...nals Designation 1 16 162708 09899E00 Spring connection 2 5 mm2 with catch and test jacks 16 pin black for conencting the Ex nL Ex nA field signals Designation 1 16 162710 Labeling strips 05869E00 FB...

Страница 15: ......

Страница 16: ...us of an IS1 field station and the fieldbus which connects the field station with the automation system The gateway is constructed as a dual processor system The I O processor controls the data exchan...

Страница 17: ...itation Lo La mH Co Ca F CL I DIV 2 A B Zone 2 GP IIC 2 0 0 466 CL I DIV 2 C G Zone 2 GP IIB IIIC 20 2 78 CL I DIV 2 D Zone 2 GP IIA 100 11 2 Notes 1 For connection of AEx nL circuits per Entity conce...

Страница 18: ...fe system should not use or generate voltages 250 V U 5 Connect either non I S circuits or Ex nL types of circuits 6 Do not disconnect Non I S field wiring unless area is known to be non hazardous Mec...

Отзывы: