IS1 I/O-Modules
Analog Output Module HART for Installation in Zone 2 Type 9466/15
6
S-BA-9466/15-08-12-0
-en-
/1
/20
162468 / 9466602310
www.stahl.de
2
perating Instructions for the IS1-System
Electrical connection
Ex nL / nA field signals
Plug-in terminals 16-pole with catch, 2.5 mm
2
, screw- or spring-type versions
Installation conditions
Assembly type
on 35 mm DIN rail NS 35/15
Installation position
horizontal and vertical
Ambient conditions
Ambient temperature
- 20 °C ... + 65 °C
Storage temperature
- 40 °C ... + 70 °C
Maximum relative humidity 95 % (no condensation)
Vibration sinusoidal
(IEC EN 60068-2-6)
1 g in the frequency range between 10 ... 500 Hz
2 g in the frequency range between 45 ... 100 Hz
Semi-sinusoidal shock
(IEC EN 60068-2-27)
15 g (3 shocks per axis and direction)
Electromagnetic
compatibility
Tested under the following standards and regulations:
EN 61 326-1 (1998) IEC 1000-4-1...6, NAMUR NE 21
Engineering notes
• Versions 946./.5 only for installation in Zone 2 or in safe area.
• Mixing of Zone 1 modules (946./.2) and Zone 2 modules (946./.5) on same BusRail is allowed.
• For separation between intrinsically safe and non-intrinsically safe circuits (
)
50 mm) a partition
plate (94 909 01 54 0) is required.
Technical Data
Dimension drawings (all dimensions in mm) - subject to alteration
09879E00