Mounting and installation
18
243137 / 640260300020
2015-12-22·BA00·III·en·05
Linear Luminaire with LED
Series EXLUX 6402/2
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Through wiring
7.3.3 Cable Entries
The standard luminaire is delivered with 3 lead-in holes, 2 cable glands and
2 stopping plug.
Please observe the tightening torque for luminaires with installed cable glands and
stopping plugs from R. STAHL Schaltgeräte GmbH.
Standard:
Spring clamp terminals
up to 4 mm
2
Optional:
Screw-type terminals
up to 4 mm
2
finely and
extra finely stranded,
and 6 mm
2
solid
Stripping length:
10 ... 11 mm
Stripping length:
10 ... 11 mm
15516E00
15438E00
NOTE
Through wiring with 2.5 mm
2
cross-section for max. 16 A.
Tightening torque
Connection thread
Pressure screw
Cable gland 8161
M20 x 1.5
2.3 Nm
1.5 Nm
M25 x 1.5
3.0 Nm
2.0 Nm
Stopping plugs 8290
M20 x 1.5
1.0 Nm
N
L1
L2
L3
L3
L2
L1
N
L1, L2, L3 = Phase
N
= Neutral conductor
PE
= Protective conductor