272350 / 610260300020
2019-07-25·BA00·III·en·00
Annex A
33
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Compact Luminaire with LED
Series C-Lux 6102/1, Series C-Lux 6109/1
For further technical data, see r-stahl.com.
Connection
6102/1:
Standard: 5-pole: L1, L2, L3, N, PE
With address module: 5-polig: L+, N-, L', N', PE
With DALI: 7-pole: L1, L2, L3, N, PE, D1, D2
6109/1:
Standard: 6-pole: L1, L2, L3, L', N, PE
With DALI: 8-pole: L1, L2, L3, L', N, PE, D1, D2
Mounting
Luminaire
Accessories
The light panel, diffuser and deflection optics are each installed with
2 compensation springs and mounting screws
Optional
DALI-connection
DALI interface in accordance with IEC 62386-207:2009-08
Control gear
(series 6109/1 only)
Emergency light
mode
In the case of a power failure, the luminaire is supplied by the battery
Rated operating
time
At optimal ambient temperature of the battery:
Switchover voltage
From mains to battery operation at U < 0.74 x U
N
From battery to mains operation at U > 0.8 x U
N
Battery set
(series 6109/1 only)
Version
NiCd battery, gas-tight, installed in the luminaire
Operating voltage
6 V
Capacity
2.2 Ah
Replacing the
battery set
When opening the enclosure, the battery set is disconnected from the
power supply;
after loosening the battery mounting screw (TX20) and the battery plug,
the battery set can be taken out of the enclosure.
Technical Data
Direct:
By means of 2 integrated fastening clips on the enclosure
for screws with a max. diameter of 6 mm
With wall bracket
(optional):
For mounting with the light panel or direct radiation
downwards on the wall
With bracket for
rope/chain
mounting
(optional):
For mounting on the chain or rope
Battery
capacity
Operating time of
emergency light
Emergency light output
2.2 Ah
1.5 h
50 %
3.0 h