Commissioning
22
272350 / 610260300020
2019-07-25·BA00·III·en·00
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Compact Luminaire with LED
Series C-Lux 6102/1, Series C-Lux 6109/1
Luminaires with cable entries and stopping plugs which are not supplied by
R. STAHL Schaltgeräte GmbH
Please observe the following:
• the required dust resistance!
• the required type of protection!
• the required temperature resistance!
• the IP degree of protection according to the rating plate!
• the operating instructions of the cable entries and stopping plugs!
• the required tightening torques!
• the range of the permissible cable diameter!
• insert the metal cable entries and/or stopping plugs into the PE!
7
Commissioning
Before commissioning, carry out the following inspection steps:
Monitor the mounting and installation.
Inspect the enclosure for damage.
Remove any foreign objects.
If necessary, clean the connection chamber.
Monitor whether the electrical lines have been inserted correctly.
Monitor whether the electrical lines are securely fitted using the cable holders provided.
Monitor whether all screws and nuts have been tightened firmly.
Monitor whether all drilled holes are closed.
Monitor whether all cable entries and stopping plugs have been tightened firmly.
Monitor whether all conductors have been connected firmly.
Monitor whether the line voltage and the rated operational voltage are consistent.
Monitor whether the permissible conductor diameter for the corresponding cable entries
have been used.
Monitor whether the device is closed according to regulations.
Monitor whether the LED assembly and the diffuser are clean.
DANGER! Explosion hazard due to defective sealing of the device!
Non-compliance may result in serious or even fatal injuries.
Equip the enclosure only with suitable equipment (e.g. cable entries,
stopping plugs or breathers) that is verifiably approved for use in hazardous areas
and meets the requirements of the IP protection rating.
Observe the operating instructions from the manufacturers of the components and
seals that are to be installed.
Seal any unused cable entries with the stopping plugs approved for the type of
protection.
Seal all open drilled holes using suitable equipment.
In order to avoid condensation in the device, observe the following:
Operate the luminaire continuously or periodically over extended periods of time.
Avoid thermal bridges.
Use breathers.