Compact Luminaire with LED
Series C-Lux 6102/1, Series C-Lux 6109/1
Connection of remote switch to control gear
Connecting the remote switch to the potential-free contact "Remote switch" of the
control gear.
Through wiring of the mains supply connection
6.2.2 Luminaires with address module
The address module is integrated into the control gear. Each control gear with an integrated
address module has a unique serial number. This serial number is right on the control gear
and can also be recorded with a QR code scanner. The luminaire address is assigned either
using the configuration software for the central battery unit or right at the central battery unit
itself.
6.2.3 Cable entries
The standard luminaire is delivered with 3 entries, 2 cable entries and 2 stopping plugs.
Tightening torques for components from R. STAHL Schaltgeräte GmbH
Luminaires with installed cable entries and stopping plugs from
R. STAHL Schaltgeräte GmbH must be tightened using the following values:
20716E00
Clamping range:
1.5 mm
2
solid, finely and extra finely stranded
Stripping length:
8.5 to 9.5 mm
Through wiring with 2.5 mm
2
cross section for max. 16 A.
There are four removable labels on the control gear (1x label for the control gear,
1x label for the exterior luminaire, 2x for customer documents).
During the installation, write down the location and position of the luminaire and the serial
number. This simplifies configuration of the central battery unit.
More information on configuration can be found in the software description and the
central battery unit manual.
Tightening torque
Connection thread
Pressure screw
Cable entry
8161
M20 x 1.5
2.3 Nm
1.5 Nm
M25 x 1.5
3.0 Nm
2.0 Nm
Stopping plug
8290
M20 x 1.5
1.0 Nm
–
M25 x 1.5
1.5 Nm
–
L
L‘
BAT+
2
3
4
5
6
7
N
BAT-
Remote Switch