Terminal Boxes
Series 8118/1, Series 8118/2
Depending on the operating voltage, perform the following safety measures:
5.3.3 Fuses
When fitting fuses, the associated ambient temperature values for the following temperature
classes apply:
When fitting fuses, the ambient temperature values for areas with dust explosion hazard for
the following max. permissible surface temperatures apply:
Operating voltage > 275 V:
20702E00
Operating voltage 275 to 440 V:
20700E00
Maintain one detent distance
between the terminals.
Install a mounting foot between
the terminal sides of the holder.
Installing, modifying or retrofitting fuses is only allowed to be performed by R. STAHL!
Fuse current value
Temperature class
(
2 A
T6
> 2 A to
(
5 A
T5
> 5 A to < 6.3 A
T4
Fuse current value
Ambient
temperature (Ta)
Max. permissible
surface temperature
(
2 A
(
40 °C
T80 °C
> 2 to
(
4 A
(
55 °C
T95 °C
> 4 to
(
5 A
(
40 °C
T95 °C
> 5 to < 6.3 A
(
55 °C
T130 °C