STA-RITE SR-2700 Скачать руководство пользователя страница 14

14

Relay ON Time Data: 

Shows how long relay is on in a day.

It resets to zero.

ADVANCED PROGRAMMING

To program in the Advanced Mode: 
1. Go to the 

SYSTEM

menu

2. Use the directional arrows to select Prog Mode 
3. Press the 

Change

button to switch from Basic to 

Advanced programming mode. 

4. Press the 

Programming

button on the 

MAIN MENU

and

the 

Select MPS Module

window will appear.

5. Select the desired relay group
6. Select the individual relay (for example,

‘RLY01Backwash Filters’, Figure 33). up to this point the
directions are the same for basic and advanced mode.

NOTE:

Programming in the advanced mode requires spe-

cialized training. If you are not experienced or trained in
setting up and programming a controller of this type, call
Sta-Rite at 1-800-752-0183, or get a qualified technician to
program the controller for you. Attempting Advanced
Programming of the controller with insufficient training can
cause problems in operating the filters and in controlling
your pool/spa water chemistry. 

NOTE:

If you go into the MPS Wizard menu to ‘Backwash

Configuration’ and select and confirm ‘Advanced
Programming’ you will clear all the settings on the selected
MPSs. Don’t do this unless you understand Advanced
Programming! Selecting Default restores factory defaults for
the selected RLY/MPS. 

Selecting an MPS To Configure (Figure 33)

NOTE:

If a line is deleted there is no undo; the line will

need to be re-entered. 
When the individual relay window appears (in the example,
‘RLY01 Backwash Filters’, Figure 33), select a specific com-
mand to change by touching directly on the line of the indi-
vidual command listed.

For example, the ‘RLY01 Backwash Filters’ window (Figure
33) contains Commands S01 through 04. The columns
show the following information:

CMD:

The command numbers. Sequence commands are

indicated with an ’S’ prefix. 
The 

Middle column

shows the text commands (entered

through the keyboard window). It is followed by 

Times

, if

needed.

SEQ: 

The sequence number(s) (if any) associated with this

command. Each command will be valid only when operat-
ing in the sequence(s) associated with it. Up to four
sequences may be specified for each command. (See

Normal CMD

or 

Sequence CMD

, below.)

The 

D

and 

I

buttons (bottom right of window) allow com-

mands to be deleted or inserted. When the command is
touched 

D

or 

I

will be displayed between the arrows, indicat-

ing that the key was recognized. The next line touched will be
either inserted or deleted. Press the down-arrow to access
commands 6-10, 11-15, and 16-20 or to cancel 

D

or 

I

.

After selecting the command to change, the 

Change Control

Command

window (see below) will open to allow changes.

Change Control Command (Figure 34)

The 

Change Control Command

window contains all the

information (for the particular command to be changed)
that is contained in the 

Readings 

window. Touch the appro-

priate line to make changes; press 

OK

when done.

The 

Change Control Command

window items are

described as follows:

COMMAND:

When the 

COMMAND

line is touched, a list

box will be displayed with all the available commands. You
can then select a command to replace the original command. 

VALUE: 

Some commands require a value to be entered:

1. Touch the 

VALUE

line;

2. The keyboard window will appear;
3. Key in the value and touch 

Enter

4. The value will be entered and you will be returned to

the Change Control Command window.

SEQUENCES:

SEQUENCE

is a series of commands, listed

in order. During operation, the Controller automatically
evaluates these commands (to determine whether the con-
ditions are right to execute them) and then executes them
(or not) in the order in which they are listed.

RESET MENU

x

Reset Controller

Reset All Sensor Cals é

Reset Totalizers

Reset Data 

Reset MPS Total ON Timers 

Reset Overfeed Timers

Reset General Settings 

Reset MPS’s to Factory Defaults

Reset Communications

Reset All MPS Programming

Reset ON-Time Data

CHANGE  

Figure 32

RLY01 Backwash Filters

x

CMD

SEQ

S01

Sequences ON

1

02

ON if MPS NONE ON

1

03 

ON  DELAY

00:00:00

1

04

Max C Time ON

00:00:00

1

I

05

Min Time OFF

00:02:00  1 

D

Figure 33

Содержание SR-2700

Страница 1: ...ol Spa Group 293 Wright Street Delavan WI 53115 North America 800 752 0183 FAX 800 582 2217 International 262 728 5551 FAX 262 728 4461 TELEX ITT 4970245 www sta ritepool com Union City TN Delavan WI Mississauga Ont Murrieta CA Printed in U S A 2002 Sta Rite Industries Inc S612 2 20 02 ...

Страница 2: ...ns to the controller Do not remove the controller s front panel if the supply power is connected to the controller Chemical burn hazard if chemicals feed at no flow See Programming pH Page 21 8 for details CONTENTS Safety 2 Introduction 3 Initializing the SR 2700 3 Window Navigating 3 Selecting Items 3 Changing Items 3 Main Menu 4 Readings 4 Data 4 MPS Timers 5 Information 5 Manual 6 Password 6 Pr...

Страница 3: ...face is a touch panel display which gives access to most of the controller s functions and set tings through a series of menus sub menus and buttons NOTE In this text guide system menus will be indicated in BOLD CAPITAL LETTERS and sub menus will be in Bold Regular Letters On window buttons will be displayed in Bold Italic Letters Operate the SR 2700 touch panel display with a plastic sty lus or o...

Страница 4: ...ed in any order When the flow switches are enabled in the programming they allow chemical feed while there is flow but prevent feed at no flow Disable the flow switch in the program ming to allow chemical feed at no flow The Flow Window displays the following ITEM Sensor names MEAS Current measurement reading The Overfeed box follows this number An o in any box indicates that that relay is in over...

Страница 5: ...ed ON since it was last cleared DAY COUNT Not used Information Figure 8 The INFORMATION Window displays important details regarding the status of the SR 2700 listed as follows Software Version The current software revision number and the date the software was updated Power ON Cycles Displays how many times the power has been turned ON or OFF Total Hours ON Displays the total hours the SR 2700 has ...

Страница 6: ...rectly controlling the relays Relays not installed can be used as expansion MPSs SOFT RELAYS The soft relays are software relays not mechan ical relays Up to 14 soft relays or expansion relays are used to increase the capabilities of the mechanical relays when more detailed control is required You can have from 1 to 14 soft relays depending on how many relays are actually installed ALARMS There ar...

Страница 7: ...t the sensor manufacturer s guide for more infor mation on calculations NOTE The lower the K factor the higher the flow will be To calibrate the Digital Flow sensor touch the on window button Change and enter the flow constant K factor on the keyboard touch Enter Return to the Calibrate Flow menu The change will be record ed along with the sensor flow reading at the time the calibra tion was made ...

Страница 8: ...ard 2 Touch Enter 3 The window will return to the Calibrate ORP menu dis playing the entered measurement 4 Touch OK The change will be recorded along with the sensor reading at the time the calibration was made NOTE Touch Reset to clear the calibration on this sensor Example The default set point is 700 the measured PPM is 0 5 1 5 PPM is desired and the current display shows a measurement of 710 m...

Страница 9: ...l described in the following pages Use the directional arrows to highlight the settings Touch the Change button to offer choices or to access keyboard input These settings must be entered correctly as they are impor tant for calculating correct readings and troubleshooting Global Alarm Sets the percentage above or below the set point that will trip the alarm This can be disabled in the programming...

Страница 10: ...ed below It also has multiple windows accessible by a variety of buttons which offer more features When setting up Communication for the first time enter the following settings Use directional arrows to highlight the settings and touch the Change button to toggle through choices or to access the keyboard input window Rings to answer on The number of rings required before the SR 2700 will answer th...

Страница 11: ... operators to particu lar alarm conditions Touch NEXT 4 to display more pager numbers System Figure 26 The SYSTEM window contains both important data details listed below and buttons allowing access to more win dows offering more features This section explains each of these windows and how to navigate through them in order to program various devices When using the controller for the first time the...

Страница 12: ...ssure minus the low P2 or effluent pressure Flow Fl 1 Fl 2 Fl 3 These inputs are general purpose inputs which can be used either as switches or with flow inputs NOTE Connect the flow inputs only to sensors or devices that do not supply voltage NEVER CONNECT FLOW INPUTS TO DEVICES THAT SUPPLY VOLTAGE ORP The oxidation reduction potential measurement of the water This measurement is used in the calc...

Страница 13: ... has access to the service menu only In this menu the service personnel may calibrate or manually turn on relays but not change the programming There are up to three passwords at this level allowing different pass words for different people Disable Figure 31 The Global Disable feature is used to turn OFF any MPS group for the time period specified on the page Select the desired MPS group by touchi...

Страница 14: ...f needed SEQ The sequence number s if any associated with this command Each command will be valid only when operat ing in the sequence s associated with it Up to four sequences may be specified for each command See Normal CMD or Sequence CMD below The D and I buttons bottom right of window allow com mands to be deleted or inserted When the command is touched D or I will be displayed between the ar...

Страница 15: ... and Sequence Command Specify the sequence then set up that sequence s associated commands Change Control Command x COMMAND Sequences ON VALUE 7 50 SEQUENCES 1 2 3 4 SEQUENCES CMD OK Figure 34 TROUBLESHOOTING This section lists common problems with the most likely solution IMPORTANT If any problems remain after reading the guides and troubleshooting procedures please call Sta Rite direct ly at 1 8...

Страница 16: ...e Sel Spec Command to Change Change Control Command Calibration Select to Calibrate Calibrate Flow Calibrate pH Calibrate ORP Cal Calculated PPM Calibrate Temperature General General Setup Data Setup Modem Pager Test Pager s System System Menu MPS Wizard Select MPS Module Select MPS to Configure Select New Configuration Security Display Reset Menu Sensor Disable APPENDIX A MENU TREE See Pages 21 a...

Страница 17: ...ited by Health Dept requirements often to 100 PPM Table for Pools Minimum Ideal Maximum Free Chlorine PPM 1 0 1 0 3 0 3 0 Combined Chlorine PPM None None 0 2 Bromine PPM 2 0 2 0 4 0 4 0 pH 7 2 7 4 7 6 7 8 Total Alkalinity PPM 60 80 100 180 TDS PPM 300 1 000 2 000 3 000 Calcium Hardness PPM 150 300 400 500 1000 Cyamuric Acid PPM 10 30 50 150 Table for Spas Minimum Ideal Maximum Free Chlorine PPM 1 ...

Страница 18: ...ompute it first ON If Alarm ON The selected module indicates which alarm this is based ON OFF If Alarm ON The selected module indicates which alarm this is based ON ON If Overfeed 1 x 24 The MPS will turn ON if the overfeed timer has been reached for the indicated MPS ON If SET ALRM 0 x 24 The set point alarms are calculated from the alarm percentage The MPS will be ON if the indicated set point a...

Страница 19: ...s less the ON time will be linearly scaled down to less time 4 The set point is 7 5 When the pH is greater than 7 5 the MPS will be ON The following commands will modify this ON condition If there were no more commands this MPS would be ON as long as the pH was greater than 7 5 5 This command will calculate the maximum and minimum times that the relay should be ON As the current reading approaches...

Страница 20: ...Description 1 ON Sequences Turns ON the sequence the commands are using 2 Manual ON Time 00 02 00 The time that the relay stays ON when manually turned ON 3 ON if Temp 76 9 The temperature set point 4 Min Time ON 00 02 00 Turns the relay ON or if the relay is turned ON by another relay it will stay on at least this long 5 Min Time OFF 00 02 00 The minimum amount of time before the heater will turn...

Страница 21: ... x System Menu Security Reset Menu Display MPS Wizard Change Sensor See Page 24 General Setup Data Setup Modem Change See Page 24 Manually Toggle MPS Select MPS Module Password Timers Enter password on keyboard Programming pH ORP Flow Keyboard Change x Info More Backwash Cycle On Flow 1 Backwash Info Flow 2 Flow 3 Model SR2700 Programmable Control Initializing Model SR2700 Programmable Control Ini...

Страница 22: ...d Keyboard Use arrows to select sensors toggle Change to show whether sensor is installed or not Installed Sensors Change Use arrows to select sensors toggle Change to show whether sensor is installed or not Installed Sensors Change Change Rly Measure Display Setup Use Arrows to Select Items To Display use Keyboard to change relay number Display Reset Menu Use arrows to select relays to change Key...

Страница 23: ...23 ...

Страница 24: ...24 ...

Отзывы: