Security (Figure 30)

The 

Security

button, located in the 

SYSTEM Menu

, opens

the 

Main Security Setup

window.

To enter a password, use the directional arrows to highlight
the desired level and touch the 

Change

button. Use the

keyboard to enter up to ten characters. Touch 

OK

NOTE: 

Touching the top line on the keyboard will provide

additional characters to make passwords also. The pass-
word level will be displayed in the upper right corner of the
window. The SR–2700 will log the highest access level
attained since the last data logging. It contains information
on who gained access and at what time. To clear all pass-
words, move the highlighted area to CLEAR ALL and push
the 

Change

button. 

If the Master Password is forgotten, you must fax the follow-
ing information to STA-RITE to clear it:
• Serial number, 
• Model Number 
• The ‘Password Forget’ number (found on the

Information

window).  

STA-RITE will then issue a number code to clear all pass-
words. Enter this number in the 

Enter Password

sub-menu

under the 

SERVICE

menu. 

The SR–2700 requires use of the master password for access
to the 

SECURITY

menu, thus ensuring that no unauthorized

people (including Sta-Rite) can access the controller.
The security system has four security levels. It has one pass-
word for the MASTER, three passwords for OPERATORs, and
three passwords for SERVICE personnel. This allows you to
track access by giving different personnel different passwords.
The access levels are listed in the following table:

MASTER:

This password gives access to all menus including

assigning passwords.

OPERATOR:

The operator has access to all areas except for

the security setup. The operator may change programming
and calibration data. There are up to three passwords at this
level, allowing different passwords for different people.
When unattended, the SR–2700 resets to the operator level
after two minutes.

SERVICE:

Service has access to the service menu only. In

this menu the service personnel may calibrate or manually
turn on relays but not change the programming. There are
up to three passwords at this level, allowing different pass-
words for different people. 

Disable (Figure 31)

The 

Global Disable

feature is used to turn OFF any MPS

group for the time period specified on the page. Select the
desired MPS group by touching directly on the group num-
ber. The highlighted items are disabled according to pre-set
time periods. To restart a disabled MPS, press the Disable
Time twice.

Reset Menu (Figure 32)

The 

Reset Menu

button, located in the 

SYSTEM Menu

,

opens the 

Reset Menu

window. This window allows you to

reconfigure items back to the factory defaults. 
Use directional arrows to highlight the appropriate line to
reset and touch the 

Change

button. The controller will ask

“Are you Sure: 

Y or N

”. Touch the appropriate choice to

confirm that the reset should be performed. Except for reset-
ting the controller, line 1, the 

Reset Menu

will stay open for

any more additions. 
The 

Reset Menu

has various menu items listed and

described below:

Controller:

The same as turning the SR–2700 OFF and ON

without actually cycling power.

All Sensor Cals:

Clears all sensor calibration except for flow

meters. Individual sensors can be reset in the calibration
window.

Totalizers:

Clears the accumulated count for the flow

meters.

Data:

Clears the entire data memory.

MPS Total ON Timers:

Clears the cumulative MPS timers.

Overfeed Timers:

Clears the daily MPS timers.

General Settings:

Sets the general settings to factory defaults.

MPS’s to Factory Defaults:

Sets all MPSs to factory defaults

and deletes all previous programming.

Communications:

Sets the communication options to facto-

ry defaults (including the modem initialization string).

All MPS Programming: 

Clears all MPS programming.

Main Security Setup x

MASTER

:

OPERATOR

:

OPERATOR

:

OPERATOR

:

SERVICE

:

SERVICE

:

SERVICE

:

CLEAR ALL

:

Select

CHANGE

Figure 30

Highlighted Items are Disabled

x

Relays 1-10

Expand

1-14

10 Mins

Alarms

1-4

30 Mins

Pagers

1-8

4 Hrs

12 Hrs

Figure 31

Содержание SR-2700

Страница 1: ...ol Spa Group 293 Wright Street Delavan WI 53115 North America 800 752 0183 FAX 800 582 2217 International 262 728 5551 FAX 262 728 4461 TELEX ITT 4970245 www sta ritepool com Union City TN Delavan WI Mississauga Ont Murrieta CA Printed in U S A 2002 Sta Rite Industries Inc S612 2 20 02 ...

Страница 2: ...ns to the controller Do not remove the controller s front panel if the supply power is connected to the controller Chemical burn hazard if chemicals feed at no flow See Programming pH Page 21 8 for details CONTENTS Safety 2 Introduction 3 Initializing the SR 2700 3 Window Navigating 3 Selecting Items 3 Changing Items 3 Main Menu 4 Readings 4 Data 4 MPS Timers 5 Information 5 Manual 6 Password 6 Pr...

Страница 3: ...face is a touch panel display which gives access to most of the controller s functions and set tings through a series of menus sub menus and buttons NOTE In this text guide system menus will be indicated in BOLD CAPITAL LETTERS and sub menus will be in Bold Regular Letters On window buttons will be displayed in Bold Italic Letters Operate the SR 2700 touch panel display with a plastic sty lus or o...

Страница 4: ...ed in any order When the flow switches are enabled in the programming they allow chemical feed while there is flow but prevent feed at no flow Disable the flow switch in the program ming to allow chemical feed at no flow The Flow Window displays the following ITEM Sensor names MEAS Current measurement reading The Overfeed box follows this number An o in any box indicates that that relay is in over...

Страница 5: ...ed ON since it was last cleared DAY COUNT Not used Information Figure 8 The INFORMATION Window displays important details regarding the status of the SR 2700 listed as follows Software Version The current software revision number and the date the software was updated Power ON Cycles Displays how many times the power has been turned ON or OFF Total Hours ON Displays the total hours the SR 2700 has ...

Страница 6: ...rectly controlling the relays Relays not installed can be used as expansion MPSs SOFT RELAYS The soft relays are software relays not mechan ical relays Up to 14 soft relays or expansion relays are used to increase the capabilities of the mechanical relays when more detailed control is required You can have from 1 to 14 soft relays depending on how many relays are actually installed ALARMS There ar...

Страница 7: ...t the sensor manufacturer s guide for more infor mation on calculations NOTE The lower the K factor the higher the flow will be To calibrate the Digital Flow sensor touch the on window button Change and enter the flow constant K factor on the keyboard touch Enter Return to the Calibrate Flow menu The change will be record ed along with the sensor flow reading at the time the calibra tion was made ...

Страница 8: ...ard 2 Touch Enter 3 The window will return to the Calibrate ORP menu dis playing the entered measurement 4 Touch OK The change will be recorded along with the sensor reading at the time the calibration was made NOTE Touch Reset to clear the calibration on this sensor Example The default set point is 700 the measured PPM is 0 5 1 5 PPM is desired and the current display shows a measurement of 710 m...

Страница 9: ...l described in the following pages Use the directional arrows to highlight the settings Touch the Change button to offer choices or to access keyboard input These settings must be entered correctly as they are impor tant for calculating correct readings and troubleshooting Global Alarm Sets the percentage above or below the set point that will trip the alarm This can be disabled in the programming...

Страница 10: ...ed below It also has multiple windows accessible by a variety of buttons which offer more features When setting up Communication for the first time enter the following settings Use directional arrows to highlight the settings and touch the Change button to toggle through choices or to access the keyboard input window Rings to answer on The number of rings required before the SR 2700 will answer th...

Страница 11: ... operators to particu lar alarm conditions Touch NEXT 4 to display more pager numbers System Figure 26 The SYSTEM window contains both important data details listed below and buttons allowing access to more win dows offering more features This section explains each of these windows and how to navigate through them in order to program various devices When using the controller for the first time the...

Страница 12: ...ssure minus the low P2 or effluent pressure Flow Fl 1 Fl 2 Fl 3 These inputs are general purpose inputs which can be used either as switches or with flow inputs NOTE Connect the flow inputs only to sensors or devices that do not supply voltage NEVER CONNECT FLOW INPUTS TO DEVICES THAT SUPPLY VOLTAGE ORP The oxidation reduction potential measurement of the water This measurement is used in the calc...

Страница 13: ... has access to the service menu only In this menu the service personnel may calibrate or manually turn on relays but not change the programming There are up to three passwords at this level allowing different pass words for different people Disable Figure 31 The Global Disable feature is used to turn OFF any MPS group for the time period specified on the page Select the desired MPS group by touchi...

Страница 14: ...f needed SEQ The sequence number s if any associated with this command Each command will be valid only when operat ing in the sequence s associated with it Up to four sequences may be specified for each command See Normal CMD or Sequence CMD below The D and I buttons bottom right of window allow com mands to be deleted or inserted When the command is touched D or I will be displayed between the ar...

Страница 15: ... and Sequence Command Specify the sequence then set up that sequence s associated commands Change Control Command x COMMAND Sequences ON VALUE 7 50 SEQUENCES 1 2 3 4 SEQUENCES CMD OK Figure 34 TROUBLESHOOTING This section lists common problems with the most likely solution IMPORTANT If any problems remain after reading the guides and troubleshooting procedures please call Sta Rite direct ly at 1 8...

Страница 16: ...e Sel Spec Command to Change Change Control Command Calibration Select to Calibrate Calibrate Flow Calibrate pH Calibrate ORP Cal Calculated PPM Calibrate Temperature General General Setup Data Setup Modem Pager Test Pager s System System Menu MPS Wizard Select MPS Module Select MPS to Configure Select New Configuration Security Display Reset Menu Sensor Disable APPENDIX A MENU TREE See Pages 21 a...

Страница 17: ...ited by Health Dept requirements often to 100 PPM Table for Pools Minimum Ideal Maximum Free Chlorine PPM 1 0 1 0 3 0 3 0 Combined Chlorine PPM None None 0 2 Bromine PPM 2 0 2 0 4 0 4 0 pH 7 2 7 4 7 6 7 8 Total Alkalinity PPM 60 80 100 180 TDS PPM 300 1 000 2 000 3 000 Calcium Hardness PPM 150 300 400 500 1000 Cyamuric Acid PPM 10 30 50 150 Table for Spas Minimum Ideal Maximum Free Chlorine PPM 1 ...

Страница 18: ...ompute it first ON If Alarm ON The selected module indicates which alarm this is based ON OFF If Alarm ON The selected module indicates which alarm this is based ON ON If Overfeed 1 x 24 The MPS will turn ON if the overfeed timer has been reached for the indicated MPS ON If SET ALRM 0 x 24 The set point alarms are calculated from the alarm percentage The MPS will be ON if the indicated set point a...

Страница 19: ...s less the ON time will be linearly scaled down to less time 4 The set point is 7 5 When the pH is greater than 7 5 the MPS will be ON The following commands will modify this ON condition If there were no more commands this MPS would be ON as long as the pH was greater than 7 5 5 This command will calculate the maximum and minimum times that the relay should be ON As the current reading approaches...

Страница 20: ...Description 1 ON Sequences Turns ON the sequence the commands are using 2 Manual ON Time 00 02 00 The time that the relay stays ON when manually turned ON 3 ON if Temp 76 9 The temperature set point 4 Min Time ON 00 02 00 Turns the relay ON or if the relay is turned ON by another relay it will stay on at least this long 5 Min Time OFF 00 02 00 The minimum amount of time before the heater will turn...

Страница 21: ... x System Menu Security Reset Menu Display MPS Wizard Change Sensor See Page 24 General Setup Data Setup Modem Change See Page 24 Manually Toggle MPS Select MPS Module Password Timers Enter password on keyboard Programming pH ORP Flow Keyboard Change x Info More Backwash Cycle On Flow 1 Backwash Info Flow 2 Flow 3 Model SR2700 Programmable Control Initializing Model SR2700 Programmable Control Ini...

Страница 22: ...d Keyboard Use arrows to select sensors toggle Change to show whether sensor is installed or not Installed Sensors Change Use arrows to select sensors toggle Change to show whether sensor is installed or not Installed Sensors Change Change Rly Measure Display Setup Use Arrows to Select Items To Display use Keyboard to change relay number Display Reset Menu Use arrows to select relays to change Key...

Страница 23: ...23 ...

Страница 24: ...24 ...

Отзывы: