33
Click the value or attribute you want to change and click “Edit” to execute this operation of write command.
5.2.9 Debug Assistant
The Ethernet generic debugging feature can send any message to the HART and monitor the data received from
the gateway on the HART. Steps are as follows:
1. Ensure that the GT200-HT-EI’s function bit of configuration switch is in the ON state and the mode bit of
configuration switch is in the OFF state, restart the gateway. Now GT200-HT-EI is in the debug mode.
2. Use a network line to connect the GT200-HT-EI’s RJ-45 port and a computer, Open the software
“SST-HI-CFG”, Click “Tool—Debug Assistant” or click on the icon
, Interface is as follows:
In this interface, clicking “Auto-send” or “Send” will combine data head, data, and check code into one frame and
send it out. The data that the gateway receives from the HART fieldbus will be shown in the blank place below.
The Checksum button only checks part of the data. Here is an example.