User Manual
HART/EtherNet/IP Gateway
GT200-HT-EI
WWW.SSTAUTOMATION.COM
9
4 Quick Start Guide
4.1 Connection
1. Make sure the GT200-HT-EI is in the appropriate operating mode that allows for configuration. It is
recommended to set the gateway to configuration mode (configuration switches Bit 1 OFF and Bit 2 ON)
then the IP of the gateway will be fixed at 192.168.0.10.
2. Connect the GT200-HT-EI to the computer by Ethernet cable.
3. Connect the HART instruments and the power supply. Refer to the topology displayed on chapter 2.7.
4. Power on the gateway and run the SST-HI-CFG software to start the configuration process.
4.2 Configuration
The following steps give an example configuration process, but tailor your configuration to your project needs.
The GT200-HT-EI is connected with a HART instrument which supports HART protocol V5 in Multi-drop mode,
configured with the HART commands 01, 03 and 06.
For more details of the software SST-HI-CFG, please refer to
.
1. Run the SST-HI-CFG software installed on the computer. Click “Upload” on the toolbar and scan available
gateways in the network. Select the gateway and click “Sign In” to upload the configuration.
Note: Make sure that the GT200-HT-EI and your computer are in the same network segment.