5.12

Setting the Interval Length

The MPG-2 allows the user to set the internal length for the correct meter interval.  While a 15 minute
interval is almost universal for interval data and the majority of demand rates, other intervals may also
exist, like 30 or 60 minutes.
The MPG-2 uses the "I" command to set the interval length from 1 minute to 60 minutes.

I1 - EOI length 1 minute.
I2 - EOI length 5 minutes.
I3 - EOI length 10 minutes.
I4 - EOI length 15 minutes.
I5 - EOI length 30 minutes.
I6 - EOI length 60 minutes.

To enter the desire Interval length for 15 minutes for example, I4 and <Enter>.  The serial link on the
MPG-2 will return the following:
-----------------------------------
Interval Energy: 15 min.
-----------------------------------

5.13

Setting the Real Time Clock

The MPG-2 allows the user to set the internal real time clock (RTC) with an initial time using the K
command.   Once the time is set, the time will elapse until the 2nd data packet i s received from the
dongle, usually about 30 to 60 seconds after  startup.
When the 2nd packet is received the timestamp from the meter will be compared to the RTC setting and
the time adjusted to match the meter.  The clock setting feature is provided for situations where the
Zigbee transmissions from the meter may not be immediately available.  The clock is set as follows:

"KMODYYRHRMNSC<CR>"

Where: K - Command Write RTCC
MO - Month (01-12)
DY - Day of Month (1-31)
YR - Year (00-99)
HR - Hour (00-23)
MN - Minutes (00-59)
SC - Seconds      (00-59)

Note 1: CR terminates the command.
Note 2: The Firmware will calculate the correct day of week for the provided Month, Day, and Year.
Note 3: A proper date must be provided, Feb. 29th 2017 is not accepted, as it does not exist. However,
Feb. 29th. 2020 is accepted. Any improper parameter will result with a response of 'Error'.  If the month
is provided as 13, this will result in 'Error'. etc.  If the day is provided as 31 on a month that only has 30
days, response 'Error', etc.

Responses:                                             " Error" - Improper values provided or invalid command.
                                                                -  or -
                                                                - ------------------------------
                                                                06/23/19 06:06:06 DOW :1 TSR:N
                                                                - ------------------------------
Note: RTCC defaults upon power up as 1/1/2019 00:00:00.

MPG-2 Programming (cont)

Содержание MPG-2

Страница 1: ...d NEU terminals to the electrical system ground ZIGBEE WIRELESS COMMUNICATION The MPG 2 is designed to receive power monitoring information from an electric meter equipped with Zigbee wireless communi...

Страница 2: ...230 Aviation Circle Loveland CO 80538 970 461 9600 970 461 9605 fax www solidstateinstruments com MPG 2WiringDiagram vsd AMI Electric Meter w Zigbee Radio K1 Z1 Y1 K2 Z2 Y2 Out 1 Out 2 MPG 2 Wireless...

Страница 3: ...to which the MPG 2 will be paired 1 2 Hardware Installation Once you are confident that the MPG 2 s Zigbee transceiver is paired with the meter completing the installation of the physical unit is the...

Страница 4: ...ously before moving on If it is not then it is not provisioned correctly with the utility s meter Do not proceed until this step is successfully completed Make sure that the dongle has not been previo...

Страница 5: ...or 000003e8 Energy U 5 35 Wh Energy F 5 70 Wh Note that the Timestamp Demand Mulitplier and Divisor are all in hexidecimial format and this represents the identical information received from the meter...

Страница 6: ...energy value and thus the kW demand is correct To change the multiplier in the MPG 2 enter the correct multiplier in the Meter Multiplier field If you are done entering information you can press the S...

Страница 7: ...ot concerned about how or at what rate the energy is consumed at For Form C Toggle Mode Select C and Send to set the Output Form field to the Toggle Form C Mode The serial link to the MPG 2 will retur...

Страница 8: ...nable the filter mode select Enable in the Filter field Hit Send The serial link on the MPG 2 will return the following Enabled To disable the filter mode select Disable in the Filter field Hit Send T...

Страница 9: ...bout 30 to 60 seconds after startup When the 2nd packet is received the timestamp from the meter will be compared to the RTC setting and the time adjusted to match the meter The clock setting feature...

Страница 10: ...r and that the pulse value is too small The LED is latched on so that the next time you look at it this RED LED will be lit and you will have a indication that an error has occurred The operation of t...

Страница 11: ...t the factory for technical support at 970 461 9600 In the Fixed output mode shown in Figure 2 below an output pulse K Y closure only is a fixed width T1 each time the output is triggered The pulse wi...

Страница 12: ...ve energy flow See Figure 3 below Form A Signed mode A positive energy value received is added to the positive Accumulated Energy Register AER A negative energy value received is added to the negative...

Страница 13: ...CR Set into Dongle Echo mode z CR or Z CR Set Factory Defaults v CR or V CR Query Firmware version Pulse Output Mode Form c0 CR or C0 CR Pulse Output Mode Form C Disabled Form A Output Mode c1 CR or...

Страница 14: ...EOI Interval Length minutes 1 to 60 minutes 15 min default EOI Interval Length Selections i1 CR or I1 CR 1 Minute Interval i2 CR or I2 CR 5 Minute Interval i3 CR or I3 CR 10 Minute Interval i4 CR or...

Отзывы: