background image

MPG-2 Wireless Meter Pulse Generator (con't)

6.0 Operation

6.1

Communication LEDs

Upon power-up, the YELLOW comm LED should light indicating that the Zigbee dongle is enumerated, correctly initialized
and communicating with the MPG-2's processor.  Within about approximately 45 - 60 seconds, the GREEN comm LED will
blink each time a valid transmission is received from the meter.  As long as valid transmissions are received by the dongle
and successfully relayed by the MPG-2's processor, the Green comm LED will blink about once every 8-9 seconds.  If the
Green comm LED does not blink, that is an indication that the data transmissions from the meter are not being received,
may be corrupted, or in some manner are not valid transmissions.  If the Green comm LED has been blinking reliably for
some time, then stops for a while and then restarts again, this indicates that transmissions are intermittent and sporatic, or
generally means there is a problem in the dongle's ability to receive data reliably from the meter.  To correct this, change
the proximity of the MPG-2 to the meter, move it closer to the meter if possible and eliminate any metalic obstructions
between the meter and the MPG-2.  Also check to make sure that any walls or barriers between the MPG-2 and the meter
have as little metal in them as possible.  For the longest distances you must have line-of-sight.

6.2

Pulse Outputs

Outputs can be configured to be in the 

Toggle

 (Form C) mode or the 

Fixed

 (Form A) mode.  Generally speaking, the

Form C mode can be used with either 2-Wire or 3-Wire Pulse receiving devices, while the Form A mode uses only a 2-
Wire interface to the downstream (receiving) pulse device.  The choice would depend on the desired pulse format that the
receiving device prefers to see.

If the dongle is reliably receiving data from the meter and passing it on to the MPG-2's processor, then you should see the
Red and Green output LED's toggle each time the selected pulse value is reached, and the MPG-2's processor generates
a pulse.  If the pulse output value is too high and pulses are too slow, then select a lower pulse value using the
programming port and the SSI Universal Programmer program or a terminal program (See Page 6).

If pulses are being generated too rapidly, select a higher pulse output value.  The maximum number of pulses per second
is approximately 10, which means that the output's open and closed times are about 50mS each in toggle mode.  If the
calculation by the MPG-2's processor for pulse output timing exceeds 15 pulses per second, the MPG-2 will light the RED
comm LED, indicating an overflow error, and that the pulse value is too small.  The LED is "latched" on so that the next
time you look at it this RED LED will be lit, and you will have a indication that an error has occurred.  The operation of the
MPG-2 will continue even though some pulses were lost.  In this way, you can quickly determine if a pulse output value is
too small, and thus, pulses too fast at a high demand.  However, in the optimum application, pulses would not exceed
more than one pulse every 2 seconds, with a 1 pulse per second maximum.  This allows a very even and "normal" pulse
rate that as closely as possible resembles an actual KYZ pulse output from the meter.

The MPG-2 will "spread out" the pulses over the next 7 second period if a high enough watt-hour value is received in a
transmission to require that more than one pulse is generated. For example, suppose you have the Output Pulse Value of
10 wh selected.  The next 8 second transmission yields 24 wh have been used. Since 24 watt-hours exceeds the 10 watt-
hour setting, two pulses must be generated.  The first 10wh pulse will be generated immediately. About three seconds later
the second 10wh pulse will be generated. The remainder of four watt-hours stays in the accumulated energy register (AER)
awaiting the next transmission and the energy value of that transmission to be added to the contents of the AER.  Another
example: Assume 25 wh/p Output Pulse Value.  Let's say the next transmission is for 130 watt hours.  130 is greater than
25, so 5 pulses will be outtputted over the next 7 seconds, approximately one each 1.4 seconds  (7 seconds / 5 = 1.4
seconds).  The remainder of 5 wh will stay in the AER awaiting the next transmission.  Some trial and error may have to be
done for any particular building since pulse rates will change depending on maximum load. The larger you can make the
pulse value the more regular the output pulses from the MPG-2 will be.

5.3

Overranging the Output

As mentioned above, if there are too many pulses calculated to be outputted in a 7 second interval than the MPG-2 can
generate given the timing constraints, the MPG-2 will light the RED comm LED.  In this situation, simply increase the pulse
output value using the programming port, and cycle power to the MPG-2 to reset the RED comm LED. This is intended to
notify the user that a higher pulse value is needed.  As load is added to a building over time, there is some likelihood that
this will occur so be sure to consider this if/when you add load to the building. If an error condition occurs, set the Pulse
Value to a higher pulse value, for example double the current value.  Remember to change the pulse constant of your
receiving device as well, since pulses will now be worth a higher watt-hour value.  Cycle power to the MPG-2 to reset the
RED comm LED after increasing the pulse value.

Содержание MPG-2

Страница 1: ...d NEU terminals to the electrical system ground ZIGBEE WIRELESS COMMUNICATION The MPG 2 is designed to receive power monitoring information from an electric meter equipped with Zigbee wireless communi...

Страница 2: ...230 Aviation Circle Loveland CO 80538 970 461 9600 970 461 9605 fax www solidstateinstruments com MPG 2WiringDiagram vsd AMI Electric Meter w Zigbee Radio K1 Z1 Y1 K2 Z2 Y2 Out 1 Out 2 MPG 2 Wireless...

Страница 3: ...to which the MPG 2 will be paired 1 2 Hardware Installation Once you are confident that the MPG 2 s Zigbee transceiver is paired with the meter completing the installation of the physical unit is the...

Страница 4: ...ously before moving on If it is not then it is not provisioned correctly with the utility s meter Do not proceed until this step is successfully completed Make sure that the dongle has not been previo...

Страница 5: ...or 000003e8 Energy U 5 35 Wh Energy F 5 70 Wh Note that the Timestamp Demand Mulitplier and Divisor are all in hexidecimial format and this represents the identical information received from the meter...

Страница 6: ...energy value and thus the kW demand is correct To change the multiplier in the MPG 2 enter the correct multiplier in the Meter Multiplier field If you are done entering information you can press the S...

Страница 7: ...ot concerned about how or at what rate the energy is consumed at For Form C Toggle Mode Select C and Send to set the Output Form field to the Toggle Form C Mode The serial link to the MPG 2 will retur...

Страница 8: ...nable the filter mode select Enable in the Filter field Hit Send The serial link on the MPG 2 will return the following Enabled To disable the filter mode select Disable in the Filter field Hit Send T...

Страница 9: ...bout 30 to 60 seconds after startup When the 2nd packet is received the timestamp from the meter will be compared to the RTC setting and the time adjusted to match the meter The clock setting feature...

Страница 10: ...r and that the pulse value is too small The LED is latched on so that the next time you look at it this RED LED will be lit and you will have a indication that an error has occurred The operation of t...

Страница 11: ...t the factory for technical support at 970 461 9600 In the Fixed output mode shown in Figure 2 below an output pulse K Y closure only is a fixed width T1 each time the output is triggered The pulse wi...

Страница 12: ...ve energy flow See Figure 3 below Form A Signed mode A positive energy value received is added to the positive Accumulated Energy Register AER A negative energy value received is added to the negative...

Страница 13: ...CR Set into Dongle Echo mode z CR or Z CR Set Factory Defaults v CR or V CR Query Firmware version Pulse Output Mode Form c0 CR or C0 CR Pulse Output Mode Form C Disabled Form A Output Mode c1 CR or...

Страница 14: ...EOI Interval Length minutes 1 to 60 minutes 15 min default EOI Interval Length Selections i1 CR or I1 CR 1 Minute Interval i2 CR or I2 CR 5 Minute Interval i3 CR or I3 CR 10 Minute Interval i4 CR or...

Отзывы: