background image

WORKING WITH THE MPG-2 RELAY

PULSE OUTPUT MODES:

 The MPG-2 Meter Pulse Generator allows the outputs to be

configured in either the "Toggle" or "Fixed" pulse output mode.  In the 

Toggle

 mode, the

outputs alternate or toggle back and forth each time a pulse is generated.  This is
synonomous with the classic 3-Wire Pulse metering and emulates the SPST KYZ switch
model.  Figure 1 below shows the timing diagram for the "Toggle" output mode.   KY and KZ
closures or continuity are always opposite of each other.  In other words, when the KY
terminals are closed (on), the KZ terminals are open(off).  This mode is best for timing
pulses to derive demand, whether 2 or 3 wires are being used.

Contact the factory for technical support at (970)461-9600.

In the Fixed output mode, shown in Figure 2 below, an output pulse (K-Y closure only) is a
fixed width (T1) each time the output is triggered.  The pulse width (closure time) is
determined by the W  command using the Programming port.  (See Page 7.)  This mode is
best for energy 

counting

 systems but generally is not best for systems doing demand control

where pulses are timed to derive instantaneous kW  demand.  The K-Z output is not used in
the Normal/Fixed(A) mode.  However, it is used in the Signed mode.  See Page 7.

T1

Figure 2: 2-Wire Only FIXED Output Operation

K-Y Out

Open

Closed

Open

Closed

K-Z Out

Figure 1: 2-Wire or 3-Wire TOGGLE Output Operation

K-Z Out

K-Y Out

Open

Open

Closed

Closed

KY closure time

In Signed mode, with a Form A output mode selected, the K-Z output pulse represents
negative (or kWh received) energy. (See Page 7.)

Содержание MPG-2

Страница 1: ...d NEU terminals to the electrical system ground ZIGBEE WIRELESS COMMUNICATION The MPG 2 is designed to receive power monitoring information from an electric meter equipped with Zigbee wireless communi...

Страница 2: ...230 Aviation Circle Loveland CO 80538 970 461 9600 970 461 9605 fax www solidstateinstruments com MPG 2WiringDiagram vsd AMI Electric Meter w Zigbee Radio K1 Z1 Y1 K2 Z2 Y2 Out 1 Out 2 MPG 2 Wireless...

Страница 3: ...to which the MPG 2 will be paired 1 2 Hardware Installation Once you are confident that the MPG 2 s Zigbee transceiver is paired with the meter completing the installation of the physical unit is the...

Страница 4: ...ously before moving on If it is not then it is not provisioned correctly with the utility s meter Do not proceed until this step is successfully completed Make sure that the dongle has not been previo...

Страница 5: ...or 000003e8 Energy U 5 35 Wh Energy F 5 70 Wh Note that the Timestamp Demand Mulitplier and Divisor are all in hexidecimial format and this represents the identical information received from the meter...

Страница 6: ...energy value and thus the kW demand is correct To change the multiplier in the MPG 2 enter the correct multiplier in the Meter Multiplier field If you are done entering information you can press the S...

Страница 7: ...ot concerned about how or at what rate the energy is consumed at For Form C Toggle Mode Select C and Send to set the Output Form field to the Toggle Form C Mode The serial link to the MPG 2 will retur...

Страница 8: ...nable the filter mode select Enable in the Filter field Hit Send The serial link on the MPG 2 will return the following Enabled To disable the filter mode select Disable in the Filter field Hit Send T...

Страница 9: ...bout 30 to 60 seconds after startup When the 2nd packet is received the timestamp from the meter will be compared to the RTC setting and the time adjusted to match the meter The clock setting feature...

Страница 10: ...r and that the pulse value is too small The LED is latched on so that the next time you look at it this RED LED will be lit and you will have a indication that an error has occurred The operation of t...

Страница 11: ...t the factory for technical support at 970 461 9600 In the Fixed output mode shown in Figure 2 below an output pulse K Y closure only is a fixed width T1 each time the output is triggered The pulse wi...

Страница 12: ...ve energy flow See Figure 3 below Form A Signed mode A positive energy value received is added to the positive Accumulated Energy Register AER A negative energy value received is added to the negative...

Страница 13: ...CR Set into Dongle Echo mode z CR or Z CR Set Factory Defaults v CR or V CR Query Firmware version Pulse Output Mode Form c0 CR or C0 CR Pulse Output Mode Form C Disabled Form A Output Mode c1 CR or...

Страница 14: ...EOI Interval Length minutes 1 to 60 minutes 15 min default EOI Interval Length Selections i1 CR or I1 CR 1 Minute Interval i2 CR or I2 CR 5 Minute Interval i3 CR or I3 CR 10 Minute Interval i4 CR or...

Отзывы: