background image

If the building on which you are using the MPG-2 has an "Instrument-Rated" electric meter (an electric meter that has
current transformers), AND the local utility has not included this multiplier in the programming of the meter (which is
normally the case), you will have to program the Meter Multipler into the MPG-2's operating parameters.  To check out
whether or not this is needed, look at the serial output using the MPG-2's programming USB port using the SSI-UP, and
convert the demand data in hexideciminal format to to decimal data.  If the kW demand is not correct, then the meter is
sending a Secondary value, meaning that the multiplier is not included.

5.1

Multiplier (CT  Ratio or CT x PT Ratio) (Con't)

Determine the Multiplier of the facility's electric meter.  If the meter is a self-contained meter (no external current
transformers), the multiplier is 1.  The default external multiplier in the MPG-2 is one (1), so you can skip this step.  If the
utility's Zigbee transmission to the dongle includes the correct CT/PT multiplier value 

(Primary

 value), you can skip this

step also.  This is very rare on instrument-rated metering implementations however, since most utilities do not want to
program the multiplier into the meter due to conflicts with the billing process.  If you are looking at the serial data received
from the meter, you will be able to see what internal multipier is being sent in every transmission.  This will be in
hexideciminal format. What you're looking for is whether this is 1 or something else besides 1.  If, for instance, the multipler
is a decimal 160, it will be transmitted by the meter to the dongle as a hexideciminal "A0".  If the multiplier 

is

 one(1), (and

this is the standard) AND 

you know

 that that the meter's external multipler is something other than 1, you will have to

program the correct external multiplier into the MPG-2 so that the true energy value, and thus the kW demand is correct.

To change the multiplier in the MPG-2, enter the correct multiplier in the 

Meter Multiplier

 field.  If you are done entering

information you can press the "Send" box and the multiplier will be sent to the MPG-2 and will show correctly now in the
Meter Multipler field.

The USB serial link will return the current multiplier stored in the MPG-2, along with all other system settings.  The
maximum multiplier is 99999 and must be an integer (whole) number.

5.2

Programming the Output Pulse Value

The output pulse value is the number of watt-hours that each pulse is worth.  This is represented by the 

Pulse Value

 field.

The MPG-2 can be set from 1 Wh to 99999 Wh per pulse.  Select a pulse value that you think will be appropriate for your
application.  A good starting point is 100 wh/pulse.  You can adjust it up or down as needed. Larger facilities will require a
larger pulse value to keep from overranging the MPG-2's registers or the maximum number of output pulses per second.
Enter 100 in the Pulse Value field and press <Send> to set the Output Pulse Value at 100 wh/pulse.  The Pulse Value on
the SSI-UP will now show the correct value:
----------------------------------------
Pulse Value: 100 watt-hours
----------------------------------------

5.3

Set Output Mode

For one direction operation, set the MPG-2's Output Mode to 

Normal

 mode (kWh delivered).  Set the MPG-2's mode to the

Signed

 mode (kWh delivered or received) if desired for a distributed energy resource(DER) application such as solar or

wind.  In the Normal mode only positive energy (delivered) is displayed and pulses generated.  In the Signed mode,
bidirectional energy (delivered or received) can be displayed and pulses generated for each mode individually.  Use the
Output Mode field to select desired mode. The Normal mode is the default.

For Normal Mode:
Set the Mode field to Normal and press <Send> to set the Output Mode to Normal Mode.  The serial link to the MPG-2 will
return:
----------------------------------------
Normal
----------------------------------------

For Signed Mode:
Set the Mode field to Signed and press <Send> to set the Output Mode to Signed Mode.  The serial link to the MPG-2 will
return:
----------------------------------------
Signed
----------------------------------------

MPG-2 Programming

Содержание MPG-2

Страница 1: ...d NEU terminals to the electrical system ground ZIGBEE WIRELESS COMMUNICATION The MPG 2 is designed to receive power monitoring information from an electric meter equipped with Zigbee wireless communi...

Страница 2: ...230 Aviation Circle Loveland CO 80538 970 461 9600 970 461 9605 fax www solidstateinstruments com MPG 2WiringDiagram vsd AMI Electric Meter w Zigbee Radio K1 Z1 Y1 K2 Z2 Y2 Out 1 Out 2 MPG 2 Wireless...

Страница 3: ...to which the MPG 2 will be paired 1 2 Hardware Installation Once you are confident that the MPG 2 s Zigbee transceiver is paired with the meter completing the installation of the physical unit is the...

Страница 4: ...ously before moving on If it is not then it is not provisioned correctly with the utility s meter Do not proceed until this step is successfully completed Make sure that the dongle has not been previo...

Страница 5: ...or 000003e8 Energy U 5 35 Wh Energy F 5 70 Wh Note that the Timestamp Demand Mulitplier and Divisor are all in hexidecimial format and this represents the identical information received from the meter...

Страница 6: ...energy value and thus the kW demand is correct To change the multiplier in the MPG 2 enter the correct multiplier in the Meter Multiplier field If you are done entering information you can press the S...

Страница 7: ...ot concerned about how or at what rate the energy is consumed at For Form C Toggle Mode Select C and Send to set the Output Form field to the Toggle Form C Mode The serial link to the MPG 2 will retur...

Страница 8: ...nable the filter mode select Enable in the Filter field Hit Send The serial link on the MPG 2 will return the following Enabled To disable the filter mode select Disable in the Filter field Hit Send T...

Страница 9: ...bout 30 to 60 seconds after startup When the 2nd packet is received the timestamp from the meter will be compared to the RTC setting and the time adjusted to match the meter The clock setting feature...

Страница 10: ...r and that the pulse value is too small The LED is latched on so that the next time you look at it this RED LED will be lit and you will have a indication that an error has occurred The operation of t...

Страница 11: ...t the factory for technical support at 970 461 9600 In the Fixed output mode shown in Figure 2 below an output pulse K Y closure only is a fixed width T1 each time the output is triggered The pulse wi...

Страница 12: ...ve energy flow See Figure 3 below Form A Signed mode A positive energy value received is added to the positive Accumulated Energy Register AER A negative energy value received is added to the negative...

Страница 13: ...CR Set into Dongle Echo mode z CR or Z CR Set Factory Defaults v CR or V CR Query Firmware version Pulse Output Mode Form c0 CR or C0 CR Pulse Output Mode Form C Disabled Form A Output Mode c1 CR or...

Страница 14: ...EOI Interval Length minutes 1 to 60 minutes 15 min default EOI Interval Length Selections i1 CR or I1 CR 1 Minute Interval i2 CR or I2 CR 5 Minute Interval i3 CR or I3 CR 10 Minute Interval i4 CR or...

Отзывы: