ZIGBEE PULSE GENERATOR

INSTRUCTION SHEET

Z
1

Y
1

K

1

POWER CONNECTIONS

CUSTOMER'S TERMINALS

1/10
Amp

UTILITY

COMPARTMENT

CUSTOMER

COMPARTMENT

LED's

R
E
D

G
R
N

F1

2
7
7
V

1
2
0

V

N
E
U

(For 120VAC)

SOLID STATE INSTRUMENTS

a division of Brayden Automation Corp.

6230 Aviation Circle, Loveland, Colorado 80538

Phone: (970)461-9600   Fax: (970)461-9605

E-mail:[email protected]

Revision: 9/25/2020

P/N: 05910-97006E

MPG-2

Premium Solid State

MOUNTING POSITION -

 The MPG-2 may be mounted in any position but is intended to be mounted with the

hinged door on the left such that the circuit board is upright.  The MPG-2 must be mounted within 25' line-of-site of
the meter.  Actual operational distance may vary with building construction and ability for the RF signal to penetrate
building materials.  For best results, mount the MPG-2 as close to the meter as reasonably possible.

POWER INPUT -

 For 120VAC, connect 

120VAC

 "hot" lead to the 120V terminal. Connect the neutral wire to the

NEU

 terminal. For 208 to 277VAC, use the 

277V

 terminal for the "hot" lead and the 

NEU

 terminal for the neutral

power supply lead.  The 

EGND

 terminal MUST be connected to the power supply ground.  If the MPG-2 is mounted

at the meter and powered from the meter potentials, AND no true neutral exists at the meter, connect the EGND
and NEU terminals to the electrical system ground.

ZIGBEE WIRELESS COMMUNICATION -

 The MPG-2 is designed to receive power monitoring information from

an electric meter equipped with Zigbee wireless communications.  The Zigbee transceiver dongle is mounted on
the MPG-2's circuit board and may be secured with a tyrap.  Ensure that the dongle is properly seated in the USB
host socket. Do not remove.

CUSTOMER OUTPUTs -

 The customer's outputs are located at the bottom of the MPG-2 board in the customer

compartment.  There are two KYZ Form C (3-wire) dry-contact outputs for watt-hour pulses, and one End-of-
Interval (EOI) KY Form A (2-Wire) pulse output.  The two 3-wire isolated pulse outputs are provided on the MPG-2,
with output terminals K1, Y1 & Z1 and K2, Y2, & Z2.  The End-of-Interval pulse output uses terminals T1 & T2.
Transient suppression for the contacts of the solid-state relays is provided internally.  The output loads should be
limited to 100 mA at 120 VAC/VDC with maximum power dissipation of each output limited to 800mW.

FUSES -

 Fuses are 3AG fast-blow type.  One-fourth (1/4) Amp fuses (the maximum size) are supplied

standard. The KYZ outputs for Output1 and Output 2 are protected by fuses F1& F2, respectively. The EOI
output is protected by fuse F3.

Out 1

EGND

Power

Input

1/10
Amp

F2

Z
2

Y
2

K

2

T
2

T
1

Y
E
L

Out 2 EOI

F3

Zigbee USB

Dongle

USB Host Socket
for Zigbee Dongle

USB Programming
Port

OPERATION -

 See the following pages for a full explanation of the operation of the MPG-2.

1/10
Amp

Firmware Version 2.19

Содержание MPG-2

Страница 1: ...d NEU terminals to the electrical system ground ZIGBEE WIRELESS COMMUNICATION The MPG 2 is designed to receive power monitoring information from an electric meter equipped with Zigbee wireless communi...

Страница 2: ...230 Aviation Circle Loveland CO 80538 970 461 9600 970 461 9605 fax www solidstateinstruments com MPG 2WiringDiagram vsd AMI Electric Meter w Zigbee Radio K1 Z1 Y1 K2 Z2 Y2 Out 1 Out 2 MPG 2 Wireless...

Страница 3: ...to which the MPG 2 will be paired 1 2 Hardware Installation Once you are confident that the MPG 2 s Zigbee transceiver is paired with the meter completing the installation of the physical unit is the...

Страница 4: ...ously before moving on If it is not then it is not provisioned correctly with the utility s meter Do not proceed until this step is successfully completed Make sure that the dongle has not been previo...

Страница 5: ...or 000003e8 Energy U 5 35 Wh Energy F 5 70 Wh Note that the Timestamp Demand Mulitplier and Divisor are all in hexidecimial format and this represents the identical information received from the meter...

Страница 6: ...energy value and thus the kW demand is correct To change the multiplier in the MPG 2 enter the correct multiplier in the Meter Multiplier field If you are done entering information you can press the S...

Страница 7: ...ot concerned about how or at what rate the energy is consumed at For Form C Toggle Mode Select C and Send to set the Output Form field to the Toggle Form C Mode The serial link to the MPG 2 will retur...

Страница 8: ...nable the filter mode select Enable in the Filter field Hit Send The serial link on the MPG 2 will return the following Enabled To disable the filter mode select Disable in the Filter field Hit Send T...

Страница 9: ...bout 30 to 60 seconds after startup When the 2nd packet is received the timestamp from the meter will be compared to the RTC setting and the time adjusted to match the meter The clock setting feature...

Страница 10: ...r and that the pulse value is too small The LED is latched on so that the next time you look at it this RED LED will be lit and you will have a indication that an error has occurred The operation of t...

Страница 11: ...t the factory for technical support at 970 461 9600 In the Fixed output mode shown in Figure 2 below an output pulse K Y closure only is a fixed width T1 each time the output is triggered The pulse wi...

Страница 12: ...ve energy flow See Figure 3 below Form A Signed mode A positive energy value received is added to the positive Accumulated Energy Register AER A negative energy value received is added to the negative...

Страница 13: ...CR Set into Dongle Echo mode z CR or Z CR Set Factory Defaults v CR or V CR Query Firmware version Pulse Output Mode Form c0 CR or C0 CR Pulse Output Mode Form C Disabled Form A Output Mode c1 CR or...

Страница 14: ...EOI Interval Length minutes 1 to 60 minutes 15 min default EOI Interval Length Selections i1 CR or I1 CR 1 Minute Interval i2 CR or I2 CR 5 Minute Interval i3 CR or I3 CR 10 Minute Interval i4 CR or...