2.1.3 Braking capacity and module losses.
230 V single-phase or three-phase modules.
MODULE RATING
2/4
4/8
7.5/15
Resistor value
Maximum current
Pulse power
Permanent power
Maximum non repetitive duration
Repetition
Losses from modules (at
maximum power)
Low level consumption
Ω
A
kW
W
s
%
W
W
100
3.8
1.2
20
0,2
1,6
15
10
100
3.8
1.2
30
0,2
2,5
25
10
50
7.6
2.4
40
0,2
1,6
50
10
Definitions
Maximum power
: Maximum power drawn, resistance connecting is carried out at
360V
, hence,
the power drawn has a maximum resistance value equal to
360
.
Pulse power:
maximum power dissipated by the resistor, this power can only be drawn for a
short time and in compliance with a certain cycle.
Permanent power (to 25°C) :
mean power that can be dissipated on a permanent basis by the
resistor.
Maximum duration:
maximum duration, in seconds, for which the pulse power can be required
(starting from cold); the resistor must be allowed to cool down before braking again.
Module losses:
losses specific to the module, the value shown in the table is that obtained when
the module is used at maximum power.
Low-level consumption:
consumption of the low-level power supplies in Watts.