All-in-one solar charge inverter  V1.0                                                                                                                                                       4 

1. General information

 

1.1 Product overview and features

 

HYP series is a new all-in-one hybrid solar charge inverter, which integrates solar energy storage & means 
charging  energy  storage  and  AC  sine  wave  output.  Thanks  to  DSP  control  and  advanced  control 
algorithm, it has high response speed, high reliability and high industrial standard. Four charging modes 
are optional, i.e. Only Solar, Mains Priority, Solar Priority and Mains & Solar hybrid charging; and two 
output modes are available, i.e. Inverter and Mains, to meet different application requirements. 
The solar charging module applies the latest optimized MPPT technology to quickly track the maximum 
power point of the PV array in any environment and obtain the maximum energy of the solar panel in 
real time. 
Through a state of the art control algorithm, the AC-DC charging module realizes fully digital voltage 
and current double closed loop control, with high control precision in a small volume. Wide AC voltage 
input range and complete input/output protections are designed for stable and reliable battery charging 
and protection. 
Based on full-digital intelligent design, the DC-AC inverter module employs advanced SPWM technology 
and outputs pure sine wave to convert DC into AC. It is ideal for AC loads such as household appliances, 
power tools, industrial equipment, and electronic audio and video equipment. The product comes with 
a segment LCD design which allows real-time display of the operating data and status of the system. 
Comprehensive electronic protections keep the entire system safer and more stable. 

 
Features:

 

1.

 

Anti-backflow grid connection function, support for inverter and mains power hybrid output, 

support for use without battery, can be set up for on-grid power generation. 

2.

 

Two output modes: mains bypass and inverter output; uninterrupted power supply. 

3.

 

Available in 4 charging  modes:  Only Solar, Mains  Priority,  Solar Priority and Mains  & Solar 

hybrid charging.  

4.

 

Advanced MPPT technology with an efficiency of 99.9%. 

5.

 

Designed  with  a  LCD  screen  and  3  LED  indicators  for  dynamic  display  of  system  data  and 

operating status. 

6.

 

With time slot control, you can set the priority of using the mains and battery according to the 

time slot in conjunction with the local peak and valley tariffs. 

7.

 

Power saving mode available to reduce no-load loss. 

8.

 

Intelligent variable speed fan efficiently dissipate heat and extend system life. 

9.

 

Lithium battery activation by PV solar or mains, allowing access of lead-acid battery and lithium 

battery. 

10.

 

360 ° all-around protection with a number of protection functions. 

11.

 

Complete  protections,  including  short  circuit  protection,  over  voltage  and  under  voltage 

protection, overload protection, reverse protection, etc. 

 

Содержание HYP4850S100-H

Страница 1: ...All in one solar charge inverter V1 0 1 All in one solar charge inverter User Manual Product models HYP4850S100 H HYP4850U100 H...

Страница 2: ...flammable or explosive or heavily dusty areas The mains input and AC output are high voltage so please do not touch the wiring terminals The housing of the all in one solar charge inverter is hot when...

Страница 3: ...E 19 2 4 4 SCHEMATIC DIAGRAM OF PARALLEL CONNECTION IN SPILIT PHASE 22 2 4 5 SCHEMATIC DIAGRAM OF PARALLEL CONNECTION IN THREE PHASE 26 3 OPERATING MODES 32 3 1 CHARGING MODE 32 3 2 OUTPUT MODE 33 4 L...

Страница 4: ...t is ideal for AC loads such as household appliances power tools industrial equipment and electronic audio and video equipment The product comes with a segment LCD design which allows real time displa...

Страница 5: ...power the load while charging the battery If the mains or generator is not connected the system can also operate normally and the load is powered by the battery and PV module 3 Battery Provided to en...

Страница 6: ...rocker switch Dry contact port AC input port Cooling fan AC output port Battery port Grounding screw hold Cooling fan RS485 2 communication port PV port Current sharing port parallel module only Func...

Страница 7: ...All in one solar charge inverter V1 0 7 1 4 Dimension drawing...

Страница 8: ...have been tightened and the wires are secured with ties to avoid looseness of connections caused by shaking of wires during mobile application The system connection wires are selected according to a c...

Страница 9: ...m of the short circuit currents of all PV modules connected in parallel the short circuit current of the PV array shall not exceed the maximum input current Refer to the table below for PV input wire...

Страница 10: ...d inverter AC output current Maximum bypass output current Recommended circuit breaker type HYP4850S100 H 10mm2 7AW G 22A 40A 2P 40A HYP4850U100 H 10mm2 7AWG 42A 63A 2P 63A Note The wiring diameter is...

Страница 11: ...one solar charge inverter ensure that there is enough air flowing through the heat sink and space of at least 200m m to the left and right air outlets of the inverter shall be left to ensure natural...

Страница 12: ...ng the external circuit breaker and confirm that the wire used is thick enough Please refer to Section 2 2 Wiring Specifications and Circuit Breaker Selection Properly connect the AC input wire accord...

Страница 13: ...ire first and then the live wire and the neutral wire The ground wire is connected to the grounding screw hole on the cabinet through the O type terminal Ground L Live N Neutral Note The grounding wir...

Страница 14: ...rays or PV sources PV PV input positive pole PV PV input negative pole BAT wiring method Prior to wiring disconnect the external circuit breaker and confirm that the wire used is thick enough Please r...

Страница 15: ...st be installed at the battery terminal Refer to Section 2 2 Wiring Specifications and Circuit Breaker Selection to select a right circuit breaker Before wiring be sure to disconnect the circuit break...

Страница 16: ...ains Finally turn on AC loads one by one as the AC output is normal to avoid a protection action caused by a large momentary shock due to simultaneous turning on the loads simultaneously Now the machi...

Страница 17: ...all all in one solar charger inverters are connected to the same battery with BAT connected to BAT BAT connected to BAT and that the connection is correct with the same wiring length and line diameter...

Страница 18: ...be connected together But L lines of different phases cannot be joined together Other connection precautions are the same as parallel connection in single phase For specific wiring please refer to 2...

Страница 19: ...nnection in single phase For specific wiring please refer to 2 4 4 Wiring Diagram 7 Before or after connecting the system please carefully refer to the following system wiring diagram to ensure that a...

Страница 20: ...All in one solar charge inverter V1 0 20 b Three all in one solar charger inverters of the system connected in parallel...

Страница 21: ...All in one solar charge inverter V1 0 21 c Four all in one solar charger inverters of the system connected in parallel d Five all in one solar charger inverters of the system connected in parallel...

Страница 22: ...ent sharing detection line of the all in one solar charger inverter need to be locked with screws after connecting The schematic diagram is as follows 2 In case of parallel operation with multiple inv...

Страница 23: ...All in one solar charge inverter V1 0 23 b Three all in one solar charger inverters of the system connected in two phase 2 1 system...

Страница 24: ...charge inverter V1 0 24 c Four all in one solar charger inverters of the system connected in two phase 2 2 system 3 1 system d Five all in one solar charger inverters of the system connected in two p...

Страница 25: ...All in one solar charge inverter V1 0 25 3 2 system e Six all in one solar charger inverters of the system connected in two phase 5 1 system...

Страница 26: ...tem 2 4 5 Schematic diagram of parallel connection in three phase 1 The parallel communication line and current sharing detection line of the all in one solar charger inverter need to be locked with s...

Страница 27: ...verters the schematic diagram of parallel connection is as follows Parallel Operation in three phase a Three all in one solar charger inverters of the system connected in three phase 1 1 1 system b Fo...

Страница 28: ...All in one solar charge inverter V1 0 28 c Five all in one solar charger inverters of the system connected in three phase 3 1 1 system...

Страница 29: ...All in one solar charge inverter V1 0 29 2 2 1 system d Six all in one solar charger inverters of the system connected in three phase 2 2 2 system...

Страница 30: ...All in one solar charge inverter V1 0 30 3 2 1 system 4 1 1 system...

Страница 31: ...single phase parallel connection setting 31 should be set as PAL When in single phase parallel connection setting 31 should be set as follows When in three phase parallel connection all machines in p...

Страница 32: ...iven to charging by Mains Power and charging with PV power will be started only when the Mains has failed 3 Hybrid Charging hybrid charging of PV and Mains Power give priority to PV MPPT charging and...

Страница 33: ...e power grid 2 Mains First switch to inverter power supply only when Mains Power has failed which is equivalent to backup UPS and is used in regions with unstable power grid 3 Inverter First switch to...

Страница 34: ...tion buttons introduction Function Key Description Menu of Enter Exit Settings Page Number Option Increase Page Number Option Decrease Under the menu of Settings OK Enter Options Indicators introducti...

Страница 35: ...mS YMD GENERAT 2 1 3 4 5 6 START END CHARGE DISCHG BMS VOLT CURR RECOVER PV1 PV2 PAGE 9 Icon function Icon function Indicates mains power Indicates the inverter is working Indicates generator Indicate...

Страница 36: ...dicates that the current battery type of the machine is NCM battery Indicates that the current battery type of the machine is LFP battery Display the page number prompt of the main interface Indicates...

Страница 37: ...s system low temperature Indicates system over temperature Indicates system over current Indicates BMS communication failure Indicates the direction of energy flow When the system is in alarm or fault...

Страница 38: ...Rated Current Reserved Load Rated Power Parallel Mode 4 2 Setup parameters description Key Operation Instructions Enter the setting menu and exit the set ting menu please press After entering the set...

Страница 39: ...90 280V Mains input voltage range of 120V machine 90 140V 04 Battery to Mains 04 43 6V Default When the Parameter 01 BT1ST PV1ST the battery voltage is lower than the set value and the output is switc...

Страница 40: ...ded lead acid battery with constant charge voltage of 57 6V and floating charge voltage of 55 2V 08 GEL Default GEL lead acid battery with constant charge voltage of 56 8V and floating charge voltage...

Страница 41: ...rge Delay Time 13 5S Default Over discharge Delay Time when the battery voltage is lower than the Parameter 12 the inverter output is turned off upon delay of time set by this Parameter with the Set R...

Страница 42: ...ned 19 Equalized Charging Delay 19 120 Default Equalization Charging Delay with the Set Range of min 900min Step of 5min available for Flooded lead acid battery sealed lead acid battery and user defin...

Страница 43: ...upon over temperature If over temperature occurs shut down output and restart output after the temperature has dropped 25 Buzzer Alarm 25 DIS No Alarm 25 ENA Default Enable alarm 26 Mode Change Remind...

Страница 44: ...model All machines in phase 1 must be set as 3P1 All machines in phase 2 must be set as 3P2 All machines in phase 3 must be set as 3P3 1 When the output voltage set in the setting 38 is 120 Vac U mod...

Страница 45: ...r AC output of the battery and the set range is 44V 54 4V 36 Max PV charger current 36 80A default Max PV charger current Setting range 0 100A 37 Battery Recharge Recovery Point 37 52V Default After t...

Страница 46: ...ging period or battery over discharge If the sectioned discharge function is enabled at the same time the power supply mode of the system will change to AC1ST which only enable the mains charging in t...

Страница 47: ...ault Charging stops when the default charging current is less than this setting 58 Discharge alarm SOC setting 58 15 default SOC alarm when capacity is less than this set value valid when BMS communic...

Страница 48: ...e voltage 55 2V 55 2V 55 2V 36 60V Adjustable Undervoltage alarm voltage 01 fault 44V 44V 44V 36 60V Adjustable Undervoltage alarm voltage recovery point 01 fault Undervoltage alarm voltage 0 8V Low v...

Страница 49: ...V Adjustable 49 2 Adjustable Undervoltage alarm voltage 01 fault 43 6V Adjustable 46 8V Adjustable 49 6V Adjustable 46 4V Adjustable 43 2V Adjustable Undervoltage alarm voltage recovery point 01 fault...

Страница 50: ...by our company through this port and enables monitoring of the equipment running status and setting of some parameters on the computer RS485 1 RS485 2 also allows direct connection with the optional...

Страница 51: ...nnect the female connector of the inverter to the male connector of the inverter to be paralleled d Do not connect the male connector of the inverter to its female connector Female connector Male conn...

Страница 52: ...attery voltage reaches the overvoltage disconnection point the PV and the mains will be automatically stopped to charge the battery to prevent the battery from being overcharged and damaged 6 Battery...

Страница 53: ...will protect and stop the output current 16 CAN communication loss protection In parallel operation an alarm will be given when CAN communication is lost 17 Parallel connection error protection In par...

Страница 54: ...ftware protection 03 BatOpen Yes Battery not connected alarm 04 BatLowEod Yes Battery undervoltage stop discharge alarm 05 BatOverCurrHw Yes Battery overcurrent hardware protection 06 BatOverVolt Yes...

Страница 55: ...rcurrent hardware protection 17 InvShort Yes Inverter short circuit protection 19 OverTemperMppt No Buck heat sink over temperature protection 20 OverTemperInv Yes Inverter heat sink over temperature...

Страница 56: ...Yes CAN communication fault in parallel operation 35 ParaAddrErr Yes Parallel ID mailing address setting error 37 ParaShareCurrErr Yes Parallel current sharing fault 38 ParaBattVoltDiff Yes Large batt...

Страница 57: ...ted correctly and whether 33 is set to the corresponding lithium battery communication protocol 59 BMS alarm No Check the BMS fault type and troubleshoot battery problems 60 BMS battery low temperatur...

Страница 58: ...tion Reduce the use of power equipment Restart the unit to resume load output 17 Inverter short circuit protection Check the load connection carefully and clear the short circuit fault points Re power...

Страница 59: ...f high temperature or burning discoloration and tighten the screws 5 Check for dirt nesting insects and corrosion and clean up as required 6 If the arrester has failed replace in time to prevent light...

Страница 60: ...ker Efficiency 95 Conversion time bypass and inverter 10ms typical AC reverse protection Available Maximum bypass overload current 40A 63A Inverter mode Output voltage waveform Pure sine wave Rated ou...

Страница 61: ...larm shutdown voltage overvoltage alarm overvoltage recovery settable on LCD screen Power saving mode self consumption Load 50W AC Output Grid Rated Output Power W 5000W Max apparent power VA 500VA Ma...

Страница 62: ...protection Hybrid charging Max charger current specifications AC charger PV charger Max charger current can be set 100A Certified specifications Certification CE IEC62109 1 EMC certification level EN6...

Отзывы: