All-in-one solar charge inverter V1.0 14
PV
input wiring method:
①
Prior to wiring, disconnect the external circuit breaker and confirm that the wire used
is thick enough. Please refer to Section 2.2 “Wiring Specifications and Circuit Breaker
Selection”;
②
Properly connect the PV input wire according to the wire sequence and terminal
position shown in the figure below: When used in parallel connection, different
machines need to be connected to different PV arrays or PV sources.
PV+: PV input positive pole PV-: PV input negative pole
BAT
wiring method:
①
Prior to wiring, disconnect the external circuit breaker and confirm that the wire used
is thick enough. Please refer to Section 2.2 “Wiring Specifications and Circuit Breaker
Selection”. The BAT wire needs to be connected to the machine through the O-type
terminal. The O-type terminal with an inner diameter of 6mm is recommended. The O-
type terminal shall firmly press the BAT wire to prevent excessive heat generation
caused by excessive contact resistance;
②
Properly connect the BAT wire according to the wire sequence and terminal position
shown in the figure below.