All-in-one solar charge inverter V1.0 45
protocol
PAC=PACE,RDA=Ritar,AOG=ALLGRAND BATTERY,OLT=OLITER,
HWD=SUNWODA, DAQ=DAKING, WOW=SRNE, PYL=PYLONTECH,
UOL=WEILAN
34
PV grid-connected
power generation
function
[34] DIS Default
Disable this Function
[34] TOGRID
In the utility bypass state, when no battery is
connected or when the battery is full, the
surplus PV energy is fed back to the grid.
[34] TOLOAD
In the utility bypass state, when no battery is
connected or when the battery is full, the load
power is supplied by the hybrid of PV and the
utility.
35
Battery Under-
voltage Recovery
Point
[35] 52V Default
When the battery is under-voltage, the battery
voltage should be greater than this set value to
restore the inverter AC output of the battery, and
the set range is 44V~54.4V.
36
Max PV charger
current
[36] 80A
default
Max PV charger current. Setting range: 0~100A
37
Battery Recharge
Recovery Point
[37] 52V Default
After the battery is fully charged, the inverter will
stop charging, and when the battery voltage is
lower than this Value, the Inverter will resume
charging again. And the set range is 44V~54V.
38
AC Output Rated
Voltage
[38] 230Vac Default You can set: 200/208/220/240Vac
39
Charge current
limiting method
(when BMS is
enabled)
[38] LC SET
Max. battery charging current not greater than
the value of setting 【07】
[38] LC BMS
Max. battery charging current not greater than
the limit value of BMS
[38] LC INV
Max. battery charging current not greater than
the logic judgements value of the inverter.
40
1-section start
charging time
[40] 00:00:00 Default Set Range: 00: 00-23: 59: 00
41
1-section end
[41] 00:00:00 Default Set Range: 00: 00-23: 59: 00