All-in-one solar charge inverter V1.0 40
working.
[06] AC1ST
The Mains Power is charged first, and PV
charging is started only when the Mains Power
has failed
[06] PV1ST
Priority shall be given to charging by PV and
mains charging will be initiated only when the PV
has failed.
[06] ONLYPV
Only PV charging, no mains charging is enabled.
07
Maximum
Charging Current
[07] 60A Default
Set Range of 0~100A
08
Battery type
[08] USER
User-defined, all battery parameters can be set.
[08] SLd
Sealed lead-acid battery with constant charge
voltage of 57.6V and floating charge voltage of
55.2V
[08] FLd
Flooded lead-acid battery with constant charge
voltage of 57.6V and floating charge voltage of
55.2V
[08] GEL Default
GEL lead-acid battery with constant charge
voltage of 56.8V and floating charge voltage of
55.2V
[08 ]LFP14/LFP15/LFP
16
LFP14/LFP15/LFP16 are corresponding to Battery
Series of 14, 15 and 16, and their default
constant charge voltages are 49.6V, 53.2V and
56.8V respectively, which can be adjusted.
[08] NCM13/NCM14 NCM lithium battery, adjustable
09
Boost Voltage
[09] 57.6V Default
Setting of Boost Voltage: Set Range of
48V~58.4V, Step 0.4V, available when the battery
type is user-defined and lithium battery.
10
Maximum Boost
Duration
[10] 120 Default
Setting of Maximum Boost Duration, which is the
maximum charging time when the voltage
reaches the Parameter [09] when charging at