All-in-one solar charge inverter V1.0 38
Real-time data viewing method
On the LCD main screen, press the button for page turning to view the real-time data of
the machine.
Page
PV side
parameters
Battery side
parameters
Mains side
parameters
Load side
parameters
Comprehensive
parameters
1
PV Voltage
Battery Voltage
AC Voltage
Load Voltage
Current Time
2
PV Current
Battery Current
AC Current
Load Current
Current Date
3
PV Power
BMS Batt SOC
AC Power
Load Power
PV Total kWh
4
PV Today kWh BMS Batt Voltage
Reserved
Load Today kWh Load Total kWh
5
PV Temperature INV Temperature
AC Frequency Load Frequency RS485 Address
6 Maintenance Parm
Battery Rated
Voltage
Reserved
Load kVA
Soft Version
7
PV Rated Voltage
Battery Rated
Current
Reserved
Load Rated
Power
Parallel Mode
4.2 Setup parameters description
Key Operation Instructions: Enter the setting menu and exit the set ting menu, please press ,
After entering the setting menu, the parameter number [00] will flash. At this time, you can press
the and key to select the parameter code to be set. Then press to enter the
parameter editing state, at this time, the value of the parameter flashes, adjust the value of the
parameter through the and , and finally press to complete the editing of the
parameter and return to the parameter selection state.
Parameter
Number
Parameter Name
Setting options
Description
00
Exit
[00]ESC
Menu of Exit Settings
01
Supply Priority
Mode
[01] AC1ST Default
Mains Power First Mode, switch to the Inverter
only when the Mains Power has failed
[01] BT1ST
Inverter First Mode: switch to Mains Power only
when the battery is under-voltage or lower than
Parameter [04] Set Value.