Solar charge inverter V1.0 10
Recommended battery input wire diameter and switch selection
Models
Recommended
battery wiring
diameter
Rated battery
discharge
current
Maximum
charge
current
Recommended air
switch or circuit breaker
type
HF2430S80-H
30mm
2
/2AWG
140A
140A
2P—160A
HF2430U80-H
30mm
2
/2AWG
140A
140A
2P—160A
Recommended AC output wiring specifications and circuit breaker selection
Models
Recommended
AC output wiring
diameter
Rated
inverter AC
output
current
Maximum
bypass output
current
Recommended air
switch or circuit breaker
type
HF2430S80-H
6mm
2
/10AWG
14.4A
30A
2P—40A
HF2430U80-H
6mm
2
/10AWG
27.5A
40A
2P—40A
Note:
The wiring diameter is for reference only. If the distance between the PV array and the all-in-one
solar charge inverter or the distance between the all-in-one solar charge inverter and the battery is
relatively long, using a thicker wire can reduce the voltage drop to improve system performance.
Note:
The above are only recommended wiring diameter and circuit breaker. Please select the
appropriate wiring diameter and circuit breaker according to actual situations.