Solar charge inverter V1.0 28
Parameter
no.
Parameter
name
Settings
Description
27
Bypass output
when over load
[27] DIS
It is disabled to automatically switch to the
Mains when the inverter is overloaded.
[27] ENA
default
It is enabled to automatically switch to the
Mains when the inverter is overloaded.
28
Max AC charger
current
[28] 80A
default
S series model
:Max AC charger current.
Setting range: 0~80A;
[28] 40A
default
U series model
:Max AC charger current.
Setting range: 0~40A;
29
Split Phase
[29] DIS
default
Supply for industrial frequency transformer
(disabled)
[29] ENA
Supply for industrial frequency transformer
(enabled)
35
Battery
undervoltage
recovery point
[35] 26V
default
When the battery voltage is under voltage, the
battery voltage needs to recover more than this
set value before the inverter starts the output
37
Battery fully
charged
recovery point
[37] 26V
default
After the battery is fully charged, it needs to be
lower than this set voltage before it can be
recharged
38
AC output
voltage setting
(only can be set
in the standby
mode )
[38] 120Vac
default
U series model
:120Vac
default
.
Allow to set to 100Vac/105Vac/110Vac/120Vac.
The rated output power will be reduced=
(Power Rate)*(Vset/120)
[38]230Vac
default
S series model
:230Vac
default
.
Allow to set to 200/208/220/230/240Vac.
The rated output power will be reduced=
(Power Rate)*(Vset/230)