Solar charge inverter V1.0 24
Parameter
no.
Parameter
name
Settings
Description
mains. Setting range: 20V~26V. Cannot exceed
the value of [14] settings.
05
Utility to
Battery Power
Setpoint
[05]28.8V
default
When the parameter [01] =SOL/SBU, the
battery voltage is higher than the set value, and
the output is switched from the mains to the
inverter. Setting range: 24V~30V. Cannot be
lower than the value of [04] / [35] settings.
06
Charger source
priority
[06] CSO
PV priority charging; only when the PV
charging fails, the mains charging is started.
[06] CUB
Mains priority charging; only when the mains
charging fails, the PV charging is started.
[06] SNU
default
PV and Mains hybrid charging; PV charging is a
priority, and when the PV energy is insufficient,
the Mains charging supplements. When the PV
energy is sufficient, the Mains charging stops.
Note: Only when the Mains bypass output is
loaded, the PV charging and the mains
charging can work at the same time. When the
inverter works, only the PV charging can be
started.
[06] OSO
Only PV charging, with the Mains charging not
activated.
07
Max charger
current
[07] 60A
default
Max charger current (AC PV charger).
Setting range: 0~80A;
08
Battery Type
[08] USE
User-defined; all battery parameters can be set.
[08] SLd
Sealed lead-acid battery; constant-voltage
charge voltage: 28.8V, floating charge voltage:
27.6V.
[08] FLd
Vented lead-acid battery; constant-voltage
charge voltage: 29.2V, floating charge voltage:
27.6V.