Solar charge inverter V1.0 27
Parameter
no.
Parameter
name
Settings
Description
Battery
equalization
immediately
[21] ENA
default
Start equalizing charge immediately.
22
Power saving
mode
[22] DIS
default
Power saving mode disabled.
[22] ENA
After the power saving mode is enabled, if the
load is null or less than 50W, the inverter
output is turned off after a delay for a certain
period of time. When the load is more than
50W, the inverter automatic restart.
23
Restart when
over load
[23] DIS
Automatic restart when overload is disabled. If
an overload occurs and the output is turned off,
the machine will not restart.
[23] ENA
default
Automatic restart when overload is enabled. If
an overload occurs and the output is turned off,
the machine will restart after a delay of 3
minutes. After it reaches 5 cumulative times,
the machine will not restart.
24
Restart when
over
temperature
[24] DIS
Automatic restart when over temperature is
disabled. If an over-temperature shutdown
occurs, machine will not restart to turn the
output on.
[24] ENA
default
Automatic restart when over temperature is
enabled. If an over-temperature shutdown
occurs, the machine will restart when the
temperature drops.
25
Alarm enable
[25] DIS
Alarm is disabled
[25] ENA
default
Alarm is enabled
26
Beeps while
primary source
is interrupted
[26] DIS
Alarm beep is disabled when the status of the
main input source changes
[26] ENA
default
Alarm beep is enabled when the status of the
main input source changes