Solar charge inverter     V1.0                                                                                                                                                                  16 

Step 5: 

Install the terminals cover. 

 

 
Step 6: 

Turn on the all-in-one solar charge inverter 

First, close the circuit breaker at the battery terminal, and then turn the rocker switch  
on the left side of the machine to the "ON" state. The "AC/INV" indicator flashing  
indicates that the inverter is working normally. Close the circuit breakers of the PV  
array and the Mains. Finally, turn on AC loads one by one as the AC output is normal  
to avoid a protection action caused by a large momentary shock due to simultaneous 
 turning on the loads simultaneously. Now, the machine goes into a normal  
operation according to the set mode. 

 
Note:

 If power is supplied to different AC loads, it is recommended to first turn on the load with a large 

surge current. After the load is stable, turn on the load with a small surge current. 

 
Note:

 If the all-in-one solar charge inverter does not work properly or the 

LCD

 or indicator is abnormal, 

refer to Chapter 6 to handle the exceptions. 

 
 

 
 

 
 

 

Содержание HF2430S80-H

Страница 1: ...Solar charge inverter V1 0 1 Solar charger inverter User Manual Product models HF2430S80 H HF2430U80 H...

Страница 2: ...mable or explosive or heavily dusty areas The mains input and AC output are high voltage so please do not touch the wiring terminals The housing of the all in one solar charge inverter is hot when it...

Страница 3: ...WIRING 11 3 OPERATING MODES 17 3 1 CHARGING MODE 17 3 2 OUTPUT MODE 18 4 LCD SCREEN OPERATING INSTRUCTIONS 19 4 1 OPERATION AND DISPLAY PANEL 19 4 2 SETUP PARAMETERS DESCRIPTION 23 4 3 BATTERY TYPE P...

Страница 4: ...s advanced SPWM technology and outputs pure sine wave to convert DC into AC It is ideal for AC loads such as household appliances power tools industrial equipment and electronic audio and video equipm...

Страница 5: ...power the load while charging the battery If the mains or generator is not connected the system can also operate normally and the load is powered by the battery and PV module 3 Battery Provided to ens...

Страница 6: ...Cooling fan AC output port Battery port CAN communication port Cooling fan USB communication port ON OFF rocker switch RS485 communication port PV port Dry contact port Touch the key lightly Groundin...

Страница 7: ...Solar charge inverter V1 0 7 1 4Dimension drawing...

Страница 8: ...een tightened and the wires are secured with ties to avoid looseness of connections caused by shaking of wires during mobile application The system connection wires are selected according to a current...

Страница 9: ...uit currents of all PV modules connected in parallel the short circuit current of the PV array shall not exceed the maximum input current Refer to the table below for PV input wire diameter and switch...

Страница 10: ...ter AC output current Maximum bypass output current Recommended air switch or circuit breaker type HF2430S80 H 6mm 2 10AWG 14 4A 30A 2P 40A HF2430U80 H 6mm 2 10AWG 27 5A 40A 2P 40A Note The wiring dia...

Страница 11: ...solar charge inverter ensure that there is enough air flowing through the heat sink and space of at least 200m to the left and right air outlets of the inverter shall be left to ensure natural convect...

Страница 12: ...he external circuit breaker and confirm that the wire used is thick enough Please refer to Section 2 2 Wiring Specifications and Circuit Breaker Selection Properly connect the AC input wire according...

Страница 13: ...irst and then the live wire and the neutral wire The ground wire is connected to the grounding screw hole on the cabinet through the O type terminal Ground L Live N Neutral Note The grounding wire sha...

Страница 14: ...tive pole BAT wiring method Prior to wiring disconnect the external circuit breaker and confirm that the wire used is thick enough Please refer to Section 2 2 Wiring Specifications and Circuit Breaker...

Страница 15: ...e installed at the battery terminal Refer to Section 2 2 Wiring Specifications and Circuit Breaker Selection to select a right circuit breaker Before wiring be sure to disconnect the circuit breaker t...

Страница 16: ...Finally turn on AC loads one by one as the AC output is normal to avoid a protection action caused by a large momentary shock due to simultaneous turning on the loads simultaneously Now the machine go...

Страница 17: ...s preferentially used to charge the battery Only when the Mains fails the PV charging can be activated 3 Hybrid charging PV and mains hybrid charging PV MPPT charging is a priority and when PV energy...

Страница 18: ...er for charging and power supply Then the unit is equivalent to a backup UPS suitable for areas with unstable grid Switching does not affect PV charging Inverter priority mode Switch to mains supply o...

Страница 19: ...ation buttons Operation buttons introduction Indicators introduction Function buttons Description SET Enter Exit Settings menu UP Previous choice DOWN Next choice ENT Confirm Enter Options under the s...

Страница 20: ...the AC output is in an overload state Indicates that the machine has been connected to the battery indicates that the remaining battery is 0 24 indicates that the remaining battery is 25 49 indicates...

Страница 21: ...ter circuit This icon is not displayed Display battery voltage battery charge total current mains charge power AC input voltage AC input frequency PV input voltage internal heat sink temperature softw...

Страница 22: ...V PV input voltage PV OUTPUT A PV output current 4 INPUT BATT A Input battery current OUTPUT BATT A Battery output current 5 INPUT BATT KW Battery input power OUTPUT BATT KW Battery output power 6 AC...

Страница 23: ...ower than the set value of parameter 04 01 UTI default Mains priority mode switching to inverter only when the mains fails 01 SBU Inverter priority mode switching to the mains only when the battery is...

Страница 24: ...tarted 06 SNU default PV and Mains hybrid charging PV charging is a priority and when the PV energy is insufficient the Mains charging supplements When the PV energy is sufficient the Mains charging s...

Страница 25: ...and lithium battery 10 Battery boost charge time 10 120 default Boost charge maximum time setting which means the maximum charging time to reach the set voltage of parameter 09 during constant voltage...

Страница 26: ...6 Battery equalization enable 16 DIS Equalizing charge is disabled 16 ENA default Equalizing charge is enabled only valid for vented lead acid battery and sealed lead acid battery 17 Battery equalizat...

Страница 27: ...matic restart when overload is enabled If an overload occurs and the output is turned off the machine will restart after a delay of 3 minutes After it reaches 5 cumulative times the machine will not r...

Страница 28: ...ly for industrial frequency transformer enabled 35 Battery undervoltage recovery point 35 26V default When the battery voltage is under voltage the battery voltage needs to recover more than this set...

Страница 29: ...27 6V 18 30V Adjustable Undervoltage alarm voltage 01 fault 22V 22V 22V 18 30V Adjustable Undervoltage alarm voltage recovery point 01 fault Undervoltage alarm voltage 0 4V Low voltage disconnection v...

Страница 30: ...Adjustable 24 6V Adjustable 28 4V Adjustable 31 6V Adjustable Undervoltage alarm voltage 01 fault 23 4V Adjustable 26 8V Adjustable 21 6V Adjustable 24 8V Adjustable 27 8V Adjustable Undervoltage ala...

Страница 31: ...rt and enables monitoring of the equipment running status and setting of some parameters on the computer It also allows direct connection with the optional RS485 to WiFi GPRS communication module deve...

Страница 32: ...es the overvoltage disconnection point the PV and the mains will be automatically stopped to charge the battery to prevent the battery from being overcharged and damaged 6 Battery low voltage protecti...

Страница 33: ...current protection When the discharge output current of the battery is greater than the maximum value and lasts for 1 minute the AC input would switched to load 14 Battery input protection When the b...

Страница 34: ...e software protection 09 PvVoltHigh No PV overvoltage protection 10 PvBuckOCSw No Buck overcurrent software protection 11 PvBuckOCHw No Buck overcurrent hardware protection 12 bLineLoss No Mains power...

Страница 35: ...device is cooled below the recovery temperature normal charge and discharge control is resumed 13 14 Bypass overload protection inverter overload protection Reduce the use of power equipment Restart t...

Страница 36: ...gh temperature or burning discoloration and tighten the screws 5 Check for dirt nesting insects and corrosion and clean up as required 6 If the arrester has failed replace in time to prevent lightning...

Страница 37: ...Available Maximum bypass overload current 30A 40A Inverter mode Output voltage waveform Pure sine wave Rated output power VA 3300 3300 Rated output power W 3300 3300 Power factor 1 Rated output volta...

Страница 38: ...80A 0 40A Charge current error 5Adc Charge voltage range 20 33Vdc Short circuit protection Circuit breaker and blown fuse Circuit breaker specifications 30A 40A Overcharge protection Alarm and turn o...

Страница 39: ...range 15 C to 55 C Storage temperature range 25 C 60 C Humidity range 5 to 95 Conformal coating protection Noise 60dB Heat dissipation Forced air cooling variable speed of fan Communication interface...