background image

6

B

C

E

D

Desiccant

Dryer

Compressor

Aftercooler

Separator

A

Prefilter(s)

Afterfilter

A

Receiver

Receiver

(B & C)  PREFILTERS  - Adequate filtration is required upstream of the 

dryer in order to protect the desiccant bed from contamination. The fol-

lowing filtration is recommended: 

B - Particulate/Gross Liquid Removal - On heavily contaminated sys-

tems use a gross contaminant filter to remove solids and high inlet liquid 

concentrations.

C - Oil Aerosol Removal - On systems with lubri cated compressors, 

use an oil removal filter to remove oil aerosols and protect desiccant bed 

from oil contamination. 

(D)  DESICCANT DRYER 

(E)  AFTERFILTER - To ensure downstream air purity (prevent desiccant 

dust from traveling downstream) adequate filtration downstream of the 

dryer is required. Typically 1 micron filtration is specified although finer 

filtration is available.
                                                  OR

Oil Vapor Adsorber - Use as an afterfilter to remove oil vapor and its 

subsequent taste and odor and to protect down -stream components 

from solid particles 0.01 micron and larger. 
NOTE:  By-pass lines and isolation valves are recommended so that 

maintenance work can be performed without shutting off the air supply.

2.2  Physical Location

Dryer must be installed with suitable overhead protection.

  

 

2.1  Location in the compressed air system.  

NOTE:  Air Compressor should be adequately sized to handle air system 

demands as well as purge loss. Failure to take this into account could 

result in overloading air compressors and/or insufficient air supply 

downstream. 
NOTE:  It is desirable to install dryer where compressed air is at the 

lowest possible temperature (downstream of aftercoolers) and the high-

est possible pressure (upstream of pressure reducing valves) without 

exceeding the maximum working pressure.

 (Refer to Figure 2A)

(A)  AFTERCOOLER/SEPARATOR - Compressed air entering dryer must 

be cooled to at least 120°F (49°C). Use aftercooler and separator if 

higher temperatures are present. 
NOTE:  Installation of a refrigerated dryer ahead of a pressure-swing 

desiccant dryer does not increase desiccant dryer capacity or reduce 

purge flow requirements.  However a cooling unit installed ahead of the 

desiccant dryer reduces the inlet air temperature and outlet air dew point. 

2.0  INSTALLATION 

2.3  Minimum & Maximum Operating  Conditions

The compressed air supply inlet should be checked periodically to ensure 

that equipment design specifications are not exceeded. Normally the 

compressor installation includes intercoolers, aftercoolers, separators, 

receivers, or similar equipment which adequately pretreat the com-

pressed air supply in order to avoid excessively high air temperatures 

and liquid slugging of downstream equipment. 

2.3.1  Compressed air conditions 
2.3.1.1
  Maximum working pressure: Refer to Serial Number Tag.   
WARNING

Do not operate the dryer at pressures above the maximum pressure 

shown on the tag.
2.3.1.2  Minimum working pressures: 100 psig (7 barg)
2.3.1.3  Maximum  inlet  compressed  air  temperature:                                                                             

120°F  (49°C)

NOTE:  If inlet  air is higher than 120°F (49°C) the air must be pre-

cooled with an aftercooler. 
2.3.2  Ambient temperatures: 

Minimum: 

Standard units: 35°F (1.7°C) 

Units with optional low ambient package:  - 10°F  (-23°C)

Maximum: 120°F (49°C)
NOTE:  If dryer is installed in ambients below 35°F (1.7°C) heat tracing 

of the prefilters and inlet piping and valves is necessary to prevent con-

densate from freezing. If installing heat tracing, observe electrical class 

code requirements for type of duty specified.

2.4 Mounting  

Install dryer on a level pad on floor. Holes are provided in    

 

the floor stand base angles for floor anchors if desired.
NOTE: Floor anchors must be used if area is subject to vibrations.

2.5 Piping  

2.5.1  Inlet and Outlet connections

Observe location of inlet and outlet connections as indicated in Figure 

2C or 2D and connect inlet and outlet piping. 
NOTE:  All piping must be supported so as not to bear on the dryers or 

filters. 
2.5.2  Isolation valves

If isolation valves are installed, it is recommended that gate valves be 

used to ensure that dryer is pressurized slowly. This is particularly true 

if isolation valves are placed before and after pre- and afterfilters where 

rapid pressurization could cause excessive pressure drop across filter 

elements. 

FIGURE 2A

Содержание RDH-HP Series

Страница 1: ...1550G RDH HP 5200G FOR M NO 3245430 R EVI S ION 04 2014 R EAD AN D U N D E R STAN D TH I S MAN UAL PR IOR TO OPE RATI NG OR S E RVICI NG TH I S PROD UCT I N STR UCTION MAN UAL MODELS RATED FLOW REFER...

Страница 2: ...red or replaced under warranty shall be warranted for the unexpired portion of the warranty applying to the original product The foregoing is the exclusive remedy of any buyer of the manufacturer s pr...

Страница 3: ...se Do not operate dryer without mufflers installed 5 High Velocity Air Do not stand near mufflers during tower depressurization I INSTALLATION 1 Install on level surface 2 Ambient temperature range 35...

Страница 4: ...arg are possible or reduce the moisture content of compressed air when used in critical process applications These dryers continuously dry compressed air by using two identical towers each containing...

Страница 5: ...sses through purge and repressurization valve 9B normally closed and purge muffler 10B to the atmosphere After regeneration purge and repressurization valve 9B normally open closes allowing tower 4B t...

Страница 6: ...r does not increase desiccant dryer capacity or reduce purge flow requirements However a cooling unit installed ahead of the desiccant dryer reduces the inlet air temperature and outlet air dew point...

Страница 7: ...ication Air Inlet Air Outlet Left Tower Pressure Gauge Right Tower Pressure Gauge Purge Pressure Gauge Electrical Entry Inlet Pressure Gauge Outlet Pressure Gauge Automatic Condensate Drain Purge Muff...

Страница 8: ...S 3 BOSS FITTING TOP VIEW ELECTRICAL ENCLOSURE SEE DETAIL SIDE VIEW SEE AC SIDE DETAIL RIGHT TOWER PRESSURE GAGE PURGE PRESSURE GAGE PURGE PRESSURE ADJUSTMENT VALVE DESICCANT FILL PORT FRONT VIEW LEFT...

Страница 9: ...PRESSURE GAUGE PURGE PRESSURE GAUGE RIGHT TOWER PRESSURE GAUGE ELECTRICAL ENCLOSURE NEMA CLASS 4 4X POWER SWITCH 3 PRONG MALE ELECTRICAL PLUG DETAIL A TOWER PRESSURE RELIEF VALVE PURGE MUFFLER PROCESS...

Страница 10: ...TLET SHUT OFF VALVE NPS 3 4 PLACES SEE SECTION B DESICCANT FILL PORT AIRLINE AFTERFILTER HF7 76 6F S MOUNTING HOLES 1 INCH DIA 6 PLACES PURGE MUFFLER 3 1 2 X 9 1 2 FORKLIFT OPENINGS 90mm X 241mm 2 PLA...

Страница 11: ...yer without one of the above measures Exhausting air will result in noise levels above OSHA permissible levels and exhausting gas could potentially cause harm to persons or property 2 8 Initial Desicc...

Страница 12: ...enoid Energized LED Left Purge Repressurization Solenoid Energize LED Right Purge Repressurization Solenoid Energized LED Left Inlet Solenoid Energized LED DIP Switches for Economizer Setting Standard...

Страница 13: ...various inlet temperatures NOTE During start up the indicator may be yellow however it should begin to change to green within four hours 3 2 1 3 Purge Flow Indicator Every four hours check the purge...

Страница 14: ...xcessive air is discharged through the muffler on the right check if valve 5b or 5c is sticking 3 3 Shut Down 3 3 1 Depressurize dryer 3 3 1 1 Open by pass valve if one is installed and close inlet an...

Страница 15: ...0 1 43 174 120 42 0 165 42 72 75 0 273 210 1 40 174 120 43 0 169 42 72 77 0 279 200 1 37 174 120 44 0 172 42 72 79 0 286 190 1 34 174 120 46 0 177 42 72 81 0 293 180 1 30 174 120 47 0 181 42 72 84 0 3...

Страница 16: ...r dryer operation Never use hygroscopic salts of the type com monly used in deliquescent type dryers 4 1 1 Frequency of desiccant replacement Desiccant should be replaced whenever the required dew poi...

Страница 17: ...4 Test Mode WARNING Enclosure contains electricity Use caution when working inside box 4 5 1 Test Mode Standard Control Panel 4 5 1 1 Wait until point in cycle when right tower is drying and left towe...

Страница 18: ...e correct Economizer Switch and Cycle Set tings Refer to Section 3 2 3 to verify proper time sequence 5 4 Tower fails to pressurize to line pressure Purge repressurization valve won t close Excessive...

Страница 19: ...011100 4011100 4011100 1 Purge Muffler Replacement Core 3097672 1 Purge Muffler Replacement Core 72378 72378 8 Aftercooler Air Filter Silencer Replacement Core 3211091 3211091 3211091 1 Aftercooler Te...

Страница 20: ...5200G SPX 1000 Philadelphia Street Canonsburg PA 15317 1700 U S A P 724 745 1555 F 724 745 6040 E hankison rental spx com www rentaldryers com Improvements and research are continuous at SPX Specifica...

Отзывы: