Measuring Exhaust Air Flow with VE, HE, EC, and SA Filters
VE=
standard grease extraction efficiency Stainless steel baffles.
HE=
High grease extraction Efficiency Cascade baffles for Enviro applications and reducing grease
discharge from buildings.
EC=
Easy Clean Teflon – standard grease extraction efficiency baffles for hot, heavy grease laden
appliances.
SA=
Spark Arrestor – standard grease extraction efficiency, for solid fuel appliances.
Measuring Instruments:
VANAXIAL VELOMETER
Follow the instruments instruction manual to measure the exhaust volume at each filter. The instrument will either measure
the total CFM or average velocity of each filter. Hold the instrument perpendicular to the face of each filter. The
Velometer should be within 1” of the filter face for best results. Once the each filter average exhaust velocity has been
measure use Chart No.1 to convert Average Filter Face Velocity to CFM.
The total exhaust volume is the sum total of each filter CFM.
2"
VELOMETER
BAFFLE FILTER
GREASE CUP
BACK OF
HOOD
INSIDE HOOD
CANOPY
Measuring Exhaust Air
Figure 24
Exhaust Air Flow VS Average Filter Face Velocity
Baffle Filter
Average Filter Velocity
Size
100 fpm/0.5m/s
200 fpm/1.0m/s
300 fpm/1.5 m/s
in x in
mm x mm
CFM
l/s
CFM
l/s
CFM
l/s
20 x 16
508 x 406
200
94
400
189
600
283
20 x 20
508 x 508
260
123
520
245
780
368
20 x 25
508 x 635
320
151
640
302
960
453
Chart No. 1