INPUT BYPASS SWITCHES (DIP SWITCH)
Input Bypass Switches allow system operators to toggle Inputs 3
-
10 on or off. The table below offers a short descrip-
tion of each switch, and lists the factory recommended switch setting if appropriate.
Dip Switch Name
Switch Position
Switch 1 –
Input 3 bypass
On:
Constant Lubrication Mode
Off:
If providing external Lubrication mode input
(Recommended)
Switch 2 –
Input 4 bypass
On:
Constant Burst Mode
Off:
If providing external Burst Mode input
(Recommended)
Switch 3 –
Input 5 bypass
On:
If not using Nozzle 1 Low Pressure Alarm
Off:
If Nozzle 1 Low Pressure Alarm is in use
Switch 4 –
Input 6 bypass
On:
If not using Nozzle 1 High Pressure Alarm
Off:
If Nozzle 1 High Pressure alarm is in use
Switch 5 –
Input 7 bypass
On:
If not using Nozzle 2 low pressure alarm
Off:
If Nozzle 2 low pressure alarm is in use
Switch 6 –
Input 8 bypass
On:
If not using Nozzle 2 high pressure alarm
Off:
If Nozzle 2 high pressure alarm is in use
Switch 7 –
Input 9 bypass
On:
If not using Air Pressure Switch
Off:
If Air Pressure Switch is in use
(Recommended)
Switch 8 –
Input 10 bypass
On:
If not using Reservoir Level Switch
Off:
If Reservoir Level Switch is in use
(Recommended)
Figure 4.4
-
2: Input bypass switches in their factory
-
recommended
positions