IM-P323-25 CH Issue 3
45
The controller is ready to operate. Now enter the required
set point of 60°C by using the
and
keys.
And read section 5 (Automatic tuning), for the self-setting of
the PID values.
Parameter
Description
Default
New
Value
Values
tune
Tuning PID
Stop
Stop
AdPt
Adaptive tuning PID
Stop
Stop
SL. u
Set point ramp up
Off
Off
SL. d
Set point ramp down
Off
Off
S.P. L
Set point low limit
-99.9
5.0
S.P. H
Set point high limit
300.0
80.0
A2hy
Alarm 2 hysteresis
0.5
0.5
A2L.b
Alarm 2 latching and blocking
none
bloc
A3hy
Alarm 3 hysteresis
0.5
0.5
A3L.b
Alarm 3 latching and blocking
none
none
t.F iL
Time constant input filter
Off
Off
In.Sh
Input shift
Off
Off
d.Err
Error dead band
Off
Off
St.OP
Soft-start output value
Off
Off
Sa.OP
Output safety value
0.0
0.0
Second group parameters
The display will show
This is used to start the automatic
tuning. Using the table opposite,
enter the following values into these
parameters.
Press the enter key
to save the
value entered and to move to the
next parameter.
When the last parameter has been
entered, press the enter key
to
save this value.
Press the scroll key
.
The display will show:
Pass
Press the scroll key
again and
the display will return to the normal
operating mode.
Stop
tvn
£