IM-P323-25 CH Issue 3
20
When the controller is powered up
for the first time, the display shows
the following message.
This shows that the controller has
not been configured.
Input the first code ILMN , using the
up and down arrow keys, then press
the enter key. The lower display will
show
C
on2
. Now input code O for
alarm 3, then press enter.
The controller will remain in stand-by
until the configuration code is set
correctly (see section 5.6 page 36).
Alarm 2 type and function
N
Not active
0
Sensor break alarm / Loop Break Alarm
1
Process
active high
2
active low
3
Deviation
active high
4
active low
5
Band
active out
6
active in
7
Alarm 3 type and function
O
Disabled
0
Sensor break alarm / Loop Break Alarm
1
Process
active high
2
active low
3
Deviation
active high
4
active low
5
Band
active out
6
active in
7
For alarm type and function see page 30.