IM-P323-25 CH Issue 3
49
Description
Operating modes
and outputs
Control mode
Features
(at 25°C environmental temp.)
Algorithm
Proportional band (P)
Integral time (I)
Dead band
Cool relative gain
Cool cycle time
Hysteresis
Error band
Cycle time
Derivative time (D)
Overshoot control
High limit
1 double
action PID
loop or On/Off
with 1 or 2
alarms
Single
action
Double action
Heat/cool
0.5…999.9%
0.01…10.00 min
0.1…100.0 min
-10.0…10.0%
0.1…10.0%
100.0…10.0% (heat) -100.0…-10.0%(cool)
1…200 sec
0.1…10.0 digit
Control output
OP1-Relay /Triac
OP1-Relay /Triac
OP2 -Logic
OP1-Relay /Triac
OP2 Logic
OP3-Relay /Triac
OP2 Logic
OP3-Relay /Triac
On-Off algorithm
PID algorithm
Heat / cool
control action
PID algorithm
OFF = O
PID with overshoot control or On-off
OP2-Relay or logic
OP2-Relay or logic
OP1-Relay /Triac
OP3-Relay/Triac
OP3-Relay/Triac
AL3 alarm
AL2 alarm
OP3-Relay/Triac
OP1-Relay /Triac
0.1…0.10
1…200 sec
0.01…1.00