IM-P323-25 CH Issue 3
12
3.3 Wiring details
3.3.1 Power supply
Please read the safety information
and the wiring notes before
proceeding with the installation of
the controller.
The controller provides switching
power supply with multiple isolation
and internal PTC
• Nominal voltage 100 - 240V~
(-15% +10%) Frequency 50/60Hz
• Power consumption 1.6 W max
3.3.2 PV control unit
A For L-J-K-S-T thermocouple type
• Connect the wires with the polarity as
shown
• Always use compensation cable of the
correct type for the thermocouple used
• The shield, if present, must be
connected to a proper earth
B For Pt100 temperature sensor
• If a 3 wire system is used, always use
cables of the same diameter (1 mm
2
min.)
(line 20
W
/ lead maximum resistance)
• when using a 2 wire system, always use
cables of the same diameter 1mm
2
(AWG 18) and link terminals 5 and 6
C For
D
T (2xRTD Pt100) Special
When the distance between the
controller and the sensor and the sensor
is 15 m, using a cable of 1mm
2
(AWG 18) diameter, produces an
error on the measure of 1°C
R1 + R2 must be <320
W
Wire
resistance
150
W
max
For 3 wires
only 20
W
/ lead
maximum
resistance
Use wires of same
length and 1mm²
(AWG 18) size.
20
W
/ lead
maximum