6.4.10 ALARM sub-menu
An alarm is triggered at a set PV figure (TDS / conductivity).
Hysteresis – 3% (default), 0 – 100% FS, 0.1% resolution. Prevents
over-frequent switching of the alarm in a turbulent boiler. Do not set to
more than 15% unless exceptional operating conditions are present.
A further damping effect for very turbulent boilers (0 - 99s).
Only available if timer switch is fitted and selected. Bottom blowdown
alarm. In the ON position, an alarm will occur if the valve fails to lift
off the seat after the predetermined time set in the timer menu.
Select on to latch the alarm relay when the PV reaches the alarm
level. The relay will only reset when the commissioning mode is
entered (pass code protected).
Select off to alarm only when PV reaches the alarm level and switches
off when PV drops below the hysterisis.
Alarms are either all latching or all non-latching.
ALARM
PV HYST
ALARM
DELAY
ALARM
BB LIFT
ALARM
LATCH
ALARM
PV