10.8.5 TIMER MENU - Bottom blowdown (BB)
DURATION (bottom blowdown valve open time)
Ranges
0 – 999
Default
0
Resolution (steps)
1
Units
Seconds
INTERVAL (Time between bottom blowdown)
Only available if TIMER DURATION is greater than 0 seconds
Ranges
1 - 99
Default
12
Resolution (steps)
1
Units
Hours
SWITCH (If a switch is fitted to valve, select fitted)
Only available if TIMER DURATION is greater than 0 seconds
Ranges
FITTED or NONE
Default
FITTED
CLOSING (Time allowed for valve to close)
Only available if TIMER DURATION is greater than 0 seconds
Ranges
1 – 10
Default
5
Resolution (steps)
1
Units
Seconds
LIFT (Time allowed for valve to lift off the seat)
Only available if TIMER DURATION is greater than 0 seconds
Ranges
1 – 10
Default
5
Resolution (steps)
1
Units
Seconds
MODE (Allow the valve to be manually opened, closed or automatically opened
and closed under the control of the timer)
Only available if TIMER DURATION is greater than 0 seconds
Ranges
AUTO, OPEN, OFF
Default
AUTO